Disconnect electrical power supply.
➢
Loosen the screw on the bottom lid, open
the wiring hole, pass the power wire and
connect through the bottom lid.
➢
Fix the bottom lid with inflated screw on the
selected position.
➢
Connect the power cable to the terminal
block as shown on the figure below.
➢
Put the sensor on the bottom lid, close the screw tightly then electrify it and test it.
CONNECT-WIRE DIAGRAM
(See the figure on the right side)
TEST:
➢
Turn time knob anti-clockwise to the minimum setting
position; turn the LUX knob clockwise to the maximum
(SUN), Turn on electricity power, the controlled load will
not initially work, needing to preheat
within
5-30 sec.
➢
The sensor will commence operating in 5-10 sec; then
sensor is activated when receive moving signal and stop
working within 7-13sec without any other sensor signal.
➢
Turn LUX knob to minimum anti-clockwise setting, if you test it when the ambient light is
more than 3LUX, the induction load would not work after the load stops working; the load
should work if you cover the detection screen, it should stop working within 7-13sec under
no induction signal condition.
Note: when testing in daylight, please turn LUX knob to (SUN) position, otherwise the
sensor will not work!
NOTE:
➢
This product should be installed by qualified electrician only.
➢
Do not install this product on unsafe or unstable surface.
➢
There should be no hindrance and/or moving objects in front of the detection screen to
disturb the detection.
➢
Avoid installing this product near air temperature alteration zones such as air conditioning,
central heating, etc.
➢
For your safety, do not disassemble.
➢
Always read the safety icons on the product.
TROUBLESHOOTING:
➢
In case of malfunction:
a. please check if the connection-wiring is correct.
b. please check if the power load is adequate .
c. please check if the working light set corresponds to ambient light.
➢
The sensitivity is poor:
a. Please check if there is an obstacle in front of the detection screen which obstructs
the signal.
b. Please check if the ambient temperature is within optimum working parameters.
c. Please check if the induction signal source is in the detection fields.
d. Please check if the installation height corresponds to the height prescribed in the
instruction.
e. Please check if the moving orientation is correct.
➢
The sensor cannot shut off the load automatically:
a. Please check if there is continual signal in the detection field.
b. Please check the time delay settings.
c. Please check if the power supply corresponds to the instruction.
d. Please check if the temperature near the sensor tends to change abruptly, such as
in cases of proximity to air conditioner or central heating sources etc.