TROUBLESHOOTING THE SNAP PAC R-SERIES CONTROLLER
SNAP PAC R-Series Controller User’s Guide
58
Information from the controller is displayed in the window:
If information does not appear, contact Product Support. (See
.)
Solving Network Problems
If there are recurring problems in communicating with the controller, check your network. The wires, switches,
and so on in your Ethernet network are not part of the Opto 22 hardware, but any problems in your network
may affect communication with Opto 22 products.
Create a Network Diagram.
—First, create a network diagram and verify the following:
•
Cable connectors are firmly inserted.
•
The switch has power. Switch LEDs indicate that the connection is up.
•
Neither the PC nor the controller uses the switch’s uplink port.
•
The SNAP PAC R-series controller’s LNK LED is lit.
Check Ethernet Errors.
—Next, use PAC Manager to check Ethernet errors reported by the controller.
These errors indicate network problems. You will need to know the controller’s IP address.
1.
Choose Start
Programs
Opto 22
PAC Project
PAC Manager.
2.
In the PAC Manager main window, click the Inspect icon
.
3.
In the IP Address field, type the IP address of the controller. Click Status Read.
4.
Scroll down until you see the items Ethernet Errors: Late Collisions, Ethernet Errors: Excessive Collisions,
and Ethernet Errors: Others.
Date and time
data was last
read
Click to
update data
Содержание SNAP PAC R SERIES
Страница 2: ......
Страница 8: ...SNAP PAC R Series Controller User s Guide vi...
Страница 72: ...TROUBLESHOOTING I O MODULES FREQUENTLY ASKED QUESTIONS SNAP PAC R Series Controller User s Guide 64...
Страница 78: ...SNAP POWER SUPPLIES SNAP PAC R Series Controller User s Guide 70...
Страница 82: ...SNAP PAC R Series Controller User s Guide 74...