CHAPTER 3: INSTALLATION AND WIRING
B1 and B2 User’s Guide
13
13
Installing Digital I/O Modules
CAUTION: Be sure that all Optomux unit power and power to the controlled devices is removed before
installing or removing I/O modules. Each position on a digital mounting rack can accept either input or
output modules. Install the color-coded I/O modules on the IO mounting rack by inserting the module pins
in the sockets on the rack. Secure the modules with the captive Phillips-head screw.
Each power I/O module is connected to two barrier strip terminals on the I/O mounting rack. When
connecting DC loads or input, the lower-numbered terminal is always more positive.
For detailed information concerning module specifications and wiring, refer to the module data
sheets. Digital Optomux units only accept modules with 5-volt logic (for example, IDC5).
Each digital I/O mounting rack is supplied with an individual 5-amp fuse for each module position.
The fuse is installed in a pair of sockets and may be removed with needle-nose pliers.
Figure 2-3: Digital Mounting Rack
10
9
8
7
6
5
4
3
2
1
7
6
5
4
3
2
1
11 12 13 14 15 16
0
I/O MODULE
1A FUSE
1A FUSE
PIN 49
ON
PWR
P1
PIN 1
5V JUMPERS
BRAIN CONNECTION
5V RETURN
+5 VDC
FIELD WIRING
FUSE
+5 GND
+5 GND
Содержание Optomux B1
Страница 1: ...B1 AND B2 USER S GUIDE Form 1574...
Страница 9: ...FOR HELP B1 and B2 User s Guide 4...
Страница 26: ...CHAPTER 3 INSTALLATION AND WIRING B1 and B2 User s Guide 21 21 Figure 2 7 Jumper Addresses...
Страница 29: ...SURGE PROTECTION FOR RS 422 485 COMMUNICATION LINKS B1 and B2 User s Guide 24...
Страница 33: ...TROUBLESHOOTING QUESTIONS AND ANSWERS B1 and B2 User s Guide 28...