92
M4RTU/M4 I/O User’s Guide
WORKSHEETS
Field Wiring Worksheet Examples
¹If the daughter card you are using does not appear above, call Opto 22 for a data sheet or contact Opto 22
Product Support for wattage specifications.
²If the digital module you are using does not appear above, use the G4 Digital AC/DC Input Output module
wattage.
³If the analog module you are using does not appear above, use the G4ADX wattage.
Hardware
Watts
(W)
Quantity
(Q)
Total
(W x Q)
M4RTU/M4 I/O Base Unit
7.5
1.0
7.5
M4RTUX I/O Extender Unit
0
0
Daughter Cards¹
M4SSER
1.6
M4SARC
1.0
M4SARCF
1.1
M4SARCFR
1.6
M4SENETC
3.1
M4SENETU
1.50
M4DUALARC
0.7
M4ENET100
4.1
Digital I/O Modules:
G4 Digital AC/DC Input/Output²
0.086
G4ODC5R, G4ODC5R5
0.10
G4IDC5Q
0.43
Analog I/O Modules:
G4ADX³
1.6
G4AD3
Sourcing:
Non-Sourcing:
2.6
1.6
G4DA4
Sourcing:
Non-Sourcing:
2.2
1.1
G4DA3, G4DA8
Sourcing:
Non-Sourcing:
2.6
1.2
G4DA9, G4DA10
0.18
Powered RS-232 devices
(e.g., barcode reader)
Total Watts (TW):
_______W
Your supplied input voltage:
_______V
TW/Your supplied input voltage = Input Current
_______A
Содержание Modular M4RTU
Страница 6: ...6 M4RTU M4 I O User s Guide TABLE OF CONTENTS...
Страница 14: ...14 M4RTU M4 I O User s Guide INTRODUCTION Figure 1 3 M4RTU M4 I O Communications Configurations...
Страница 32: ...32 M4RTU M4 I O User s Guide INSTALLATION AND SETUP Figure 3 3 Installing the Power Supply on the M4RTU M4 I O...
Страница 74: ...74 M4RTU M4 I O User s Guide FIELD WIRING...
Страница 80: ...80 M4RTU M4 I O User s Guide PRODUCT SPECIFICATIONS...
Страница 82: ...82 M4RTU M4 I O User s Guide ADDRESS JUMPER CONFIGURATION...
Страница 86: ...86 M4RTU M4 I O User s Guide UPGRADING RAM AND FLASH EEPROM...
Страница 89: ...M4RTU M4 I O User s Guide 89 WORKSHEETS Figure F 3 M4RTUX I O Extender I O Module Worksheet...
Страница 91: ...M4RTU M4 I O User s Guide 91 WORKSHEETS Figure F 5 Field Wiring Worksheet Example 2...
Страница 94: ...94 M4RTU M4 I O User s Guide WORKSHEETS...
Страница 96: ...96 M4RTU M4 I O User s Guide PRODUCT SUPPORT...