DEVICENET INFORMATION
3-6
BD-DEVNET Users Guide
Table 3-12: Common Services
Service
Implemented for:
Service
Code
Class
Instance
Name
0 E
Yes
Yes
Get_Attribute_Single
10
N o
Yes
Set_Attribute_Single
4B
N o
Yes
Allocate_Master/Slave
4C
No
Yes
Release_Master/Slave
*Settable only if switch 7 and 8 are both in the ON position. Value returned will be switch 1..6 or last value set.
**Settable by switch 7 or 8 or through DeviceNet if switch 7 and 8 are both on.
Switch/Value
Speed
0
125 kbits
1
250 kbits
2
500 kbits
3
undefined
***Bus Off Interrupt (BOI) determines action if Bus Off state encountered. Following values are supported:
BOI
Action
0
Hold chip in OFF state (default)
1
If possible reset CAN chip
**** Bus Off Counter will be forced to zero whenever set, regardless of the data value provided.
***** Allocation_byte
bit 0
explicit
set to 1 to allocate
bit 1
polled
set to 1 to allocate
bit 2
strobed
(not supported)
bit 3-7
reserved
always 0
Table 3-11: DeviceNet Object, Instance 1 Attributes
Attr
Access
Name
Ty p e
Value
1
Get/Set
MAC ID
USINT
*
2
Get/Set
Baud Rat
USINT
**
3
Get/Set
Bus Off Interrupt
BOOL
***
4
Get/Set
Bus Off Counter
USINT
****
5
Get/Spc
Allocation Info
STRUCT of
*****
Choice Byte
BYTE
Master Node Addr.
USINT