4-1-3 Placement and Environment
(1)
A UPS should be placed in a clean and air conditioned environment and with ambient temperature
between 0
℃
and +28
℃
. The operation temperature ranging from 10
℃
to +25
℃
is the best.
(2)
UPS can’t be closely placed against or surrounded by walls or other objects as it would prevent from
good ventilation. An exhaust is in a rear of the UPS shown as Fig. 4-1-3a.
(3)
Make room for opening the door of the UPS cabinet. For ventilation and maintenance purposes the
distances to walls or objects should be at least as shown in Fig. 4-1-3b and Fig.4-1-3c.
(4)
The BTU values for DS-C33 II series shown as table 4-1-3d.
(5)
The chamber for UPS placement should be sufficiently lit and equipped with an emergency fire
extinction system.
15cm
15cm
50cm
50cm
90cm
door
Top View
Fig. 4-1-3a Fig. 4-1-3b Fig. 4-1-3c
Table 4-1-3d BTU Values
Model
BTU
DS 10KC33 II
3542
DS 15KC33 II
5313
DS 20KC33 II
6539
DS 30KC33 II
9808
DS 45KC33 II
13486
DS 60KC33 II
16347
DS 80KC33 II
21796
DS 100KC33 II
24520
DS 120KC33 II
29424
DS 160KC33 II
34873
DS 200KC33 II
43592
Содержание DS 100KC33 II
Страница 1: ...DS C33 II Series User s Manual www opti ups com ...
Страница 14: ...U P S Fig 4 1 1c Fig 4 1 1d Fig 4 1 1e ...
Страница 17: ...4 1 4 Outline and Dimension 10 15 20 30K 120V 208V 220V 380V Models ...
Страница 18: ...45 60K 120V 208V Models 45 60 80 100 120K 220V 380V Models ...
Страница 19: ...80 100 120K 120V 208V Models ...
Страница 20: ...160 200K 220V 380V Models ...
Страница 25: ...80 100 120K 120V 208V Models Slave UPS I R I S I T I N B G B BP R BP S BP T BP N O N O R O S O T ...