TROUBLE SHOOTING 

Problem 

LCD/LED/Buzzer 

Explanation / Possible cause 

What to do 

Unit shuts down 

automatically 

during startup 

process. 

LCD/LEDs and buzzer 

will be active for 3 

seconds and then 

complete off. 

The battery voltage is too low 

(<1.91V/Cell) 

1. Re-charge battery. 

2. Replace battery. 

No response after 

power on. 

No indication. 

1. The battery voltage is far too 

low. (<1.4V/Cell) 

2. Battery polarity is connected 

reversed. 

1. Check if batteries and the 

wiring are connected well. 

2. Re-charge battery. 

3. Replace battery. 

Mains exist but the 

unit works in 

battery mode. 

Input voltage is 

displayed as 0 on the 

LCD and green LED is 

flashing. 

Input protector is tripped 

Check if AC breaker is tripped 

and AC wiring is connected 

well. 

Green LED is flashing.  Insufficient quality of AC power. 

(Shore or Generator) 

1. Check if AC wires are too 

thin and/or too long. 

2. Check if generator (if 

applied) is working well or if 

input voltage range setting is 

correct. (UPS

Appliance) 

Green LED is flashing.  Set “Solar First” as the priority of 

output source. 

Change output source priority 

to Utility first. 

When the unit is 

turned on, internal 

relay is switched on 

and off repeatedly. 

LCD display and LEDs 

are flashing 

Battery is disconnected. 

Check if battery wires are 

connected well.   

Buzzer beeps 

continuously and 

red LED is on. 

Fault code 07 

Overload error. The inverter is 

overload 110% and time is up. 

Reduce the connected load by 

switching off some 

equipment. 

Fault code 05 

Output short circuited. 

Check if wiring is connected 

well and remove abnormal 

load.   

Temperature of internal converter 

component is over 120°C. (Only 

available for 1-3KVA models.) 

Check whether the air flow of 

the unit is blocked or whether 

the ambient temperature is 

too high. 

Fault code 02 

Internal temperature of inverter 

component is over 100°C. 

Fault code 03 

Battery is over-charged.   

Return to repair center. 

The battery voltage is too high. 

Check if spec and quantity of 

batteries are meet 

requirements. 

Fault code 01 

Fan fault 

Replace the fan. 

Fault code 06/58 

Output abnormal (Inverter voltage 

below than 190Vac or is higher 

than 260Vac) 

1. Reduce the connected 

load. 

2. Return to repair center 

Fault code 

08/09/53/57 

Internal components failed. 

Return to repair center. 

Fault code 51 

Over current or surge. 

Restart the unit, if the error 

happens again, please return 

to repair center. 

Fault code 52 

Bus voltage is too low. 

Fault code 55 

Output voltage is unbalanced. 

Fault code 56 

Battery is not connected well or 

fuse is burnt. 

If the battery is connected 

well, please return to repair 

center. 

Содержание SP Brilliant Series

Страница 1: ...Solar Hybrid Inverter SP Brilliant Series User Manual...

Страница 2: ...n 8 Final Assembly 9 Communication Connection 9 Dry Contact Signal 10 OPERATION 11 Power ON OFF 11 Operation and Display Panel 11 LCD Display Icons 12 LCD Setting 14 Display Setting 18 Operating Mode...

Страница 3: ...nnel can install this device with battery 6 NEVER charge a frozen battery 7 For optimum operation of this inverter charger please follow required spec to select appropriate cable size It s very import...

Страница 4: ...lications via LCD setting Configurable AC Solar Charger priority via LCD setting Compatible to mains voltage or generator power Auto restart while AC is recovering Overload Over temperature short circ...

Страница 5: ...ay 2 Status indicator 3 Charging indicator 4 Fault indicator 5 Function buttons 6 Power on off switch 7 AC input 8 AC output 9 PV input 10 Battery input 11 Circuit breaker 12 RS232 communication port...

Страница 6: ...ng points before selecting where to install Do not mount the inverter on flammable construction materials Mount on a solid surface Install this inverter at eye level in order to allow the LCD display...

Страница 7: ...to use appropriate cable for battery connection To reduce risk of injury please use the proper recommended cable and terminal size as below Recommended battery cable and terminal size Model Typical A...

Страница 8: ...RNING Shock Hazard Installation must be performed with care due to high battery voltage in series CAUTION Do not place anything between the flat part of the inverter terminal and the ring terminal Oth...

Страница 9: ...ble size as below Suggested cable requirement for AC wires Model Gauge Torque Value 3KVA 12 AWG 1 2 1 6 Nm 5KVA 8 AWG 1 4 1 6Nm Please follow below steps to implement AC input output connection 1 Befo...

Страница 10: ...wires with correct polarity If L and N wires are connected reversely it may cause utility short circuited when these inverters are worked in parallel operation CAUTION Appliances such as air conditio...

Страница 11: ...insulation sleeve 10 mm for positive and negative conductors 2 Check correct polarity of connection cable from PV modules and PV input connectors Then connect positive pole of connection cable to pos...

Страница 12: ...and no output is powered Close Open Power On Output is powered from Utility Close Open Output is powered from Battery or Solar Program 01 set as Utility Battery voltage Low DC warning voltage Open Cl...

Страница 13: ...ng status and input output power information LED Indicator LED Indicator Messages Green Solid On Output is powered by utility in Line mode Flashing Output is powered by battery or PV in battery mode G...

Страница 14: ...ad percent load in VA load in Watt and discharging current Battery Information Indicates battery level by 0 24 25 49 50 74 and 75 100 in battery mode and charging status in line mode In AC mode it wil...

Страница 15: ...1 867V cell 1 95V cell 1 95 2 033V cell 2 033 Load Information Indicates overload Indicates the load level by 0 24 25 50 50 74 and 75 100 0 25 25 50 50 75 75 100 Mode Operation Information Indicates u...

Страница 16: ...available Battery voltage drops to either low level warning voltage or the setting point in program 12 Utility first default Utility will provide power to the loads as first priority Solar and batter...

Страница 17: ...t be effected Saving mode enable If enabled the output of inverter will be off when connected load is pretty low or not detected 05 Battery type AGM default Flooded User Defined If User Defined is sel...

Страница 18: ...int back to utility source when selecting SBU priority or Solar first in program 01 Available options 44V 45V 46V default 47V 48V 49V 50V 51V 13 Setting voltage point back to battery mode when selecti...

Страница 19: ...ergy will be the only charger source no matter utility is available or not If this inverter charger is working in Battery mode or Power saving mode only solar energy can charge battery Solar energy wi...

Страница 20: ...8V model default setting 42 0V If self defined is selected in program 5 this program can be set up Setting range is from 40 0V to 48 0V Increment of each click is 0 1V Low DC cut off voltage will be f...

Страница 21: ...Screen Input Voltage 230V output voltage 230V Input frequency Input frequency 50Hz PV voltage PV voltage 60V MPPT Charging current Current 10A Current 10A MPPT Charging power MPPT charging power 500W...

Страница 22: ...ower than 1kVA load in VA will present xxxVA like below chart When load is larger than 1kVA 1KVA load in VA will present x xkVA like below chart Load in Watt When load is lower than 1kW load in W will...

Страница 23: ...21 Main CPU version checking Main CPU version 00014 04 Secondary CPU version checking Secondary CPU version 00003 03...

Страница 24: ...e Errors are caused by inside circuit error or external reasons such as over temperature output short circuited and so on PV energy and utility can charge batteries Charging by utility Only available...

Страница 25: ...ted or over temperature is detected by internal converter components 06 Output voltage is abnormal For 1K 2K 3K model Output voltage is too high For 4K 5K model 07 Overload time out 08 Bus voltage is...

Страница 26: ...times every second 03 Battery is over charged Beep once every second 04 Low battery Beep once every second 07 Overload Beep once every 0 5 second 10 Output power derating Beep twice every 3 seconds 12...

Страница 27: ...age 135Vac 7V or 270Vac 7V Max AC Input Voltage 150Vac or 300Vac Nominal Input Frequency 50Hz 60Hz Auto detection Low Loss Frequency 40 1Hz Low Loss Return Frequency 42 1Hz High Loss Frequency 65 1Hz...

Страница 28: ...0s 110 150 load Surge Capacity 2 rated power for 5 seconds Nominal DC Input Voltage 48Vdc Cold Start Voltage 46Vdc Low DC Warning Voltage load 20 44 0Vdc 20 load 50 42 8Vdc load 50 40 4Vdc Low DC Warn...

Страница 29: ...ing Current Voltage T1 T1 10 T0 minimum 10mins maximum 8hrs T0 2 43Vdc 2 35Vdc 2 25Vdc Solar Charging Mode INVERTER MODEL 3KVA 5KVA Rated Power 3000W Efficiency 98 0 max Max PV Array Open Circuit Volt...

Страница 30: ...nd LEDs are flashing Battery is disconnected Check if battery wires are connected well Buzzer beeps continuously and red LED is on Fault code 07 Overload error The inverter is overload 110 and time is...

Страница 31: ...7 1500 159 402 1800 123 301 2100 105 253 2400 91 219 2700 71 174 3000 63 155 5KVA 500 613 1288 1000 268 613 1500 158 402 2000 111 271 2500 90 215 3000 76 182 3500 65 141 4000 50 112 4500 44 100 5000 4...

Отзывы: