Fire Protection | Data sheet No. 49103 | Version 01-2016 |
5
|
6
Manual call point DKM 3.3 – bus capable
1.
3.
2.
4 − 7 mm
8 − 10 mm
Wiring
Страница 1: ...anager can therefore see all connected detectors at a glance Important Note Please also note separate specification sheets for STG 1 2 The manual call point consists of the plastic housing and door It contains the circuit board with terminals trigger mechanism and push button The replaceable standardized thin glass pane in a lockable door protected by a standardized lock is a safeguard against uni...
Страница 2: ... automatic fire detectors can be connected to a primary cable The test detector can be used on primary cables together with auto matic fire detectors It is connected at the electrical end of the primary cable max 1 test detector per primary cable The distance between non automatic fire detectors should be no more than 100 meters iaw DIN 14 675 and 80 meters iaw VdS Non automatic fire detectors sho...
Страница 3: ... point DKM 3 3 bus capable Installation dimensions Space requirements toward the right to open the detector 60 mm 135 mm 37 mm 135 mm 17 mm 13 mm ca 35 mm Surface mounted installation remove circuit board first In wall installation 3 4 4 x 40 mm 2x S 5 2x 5 approx 35mm ...
Страница 4: ...ry The assigned default address is 1 On request Oppermann can configure the detectors with custom BUS addresses indicate in your order The positioning of addressed DKMs in the ringbus is arbitrary A fault alarm is triggered if the same detector address is assigned twice on the ringbus If the detector address is changed the detector must be reregistered with the STG in service mode For connection t...
Страница 5: ... Fire Protection Data sheet No 49103 Version 01 2016 5 6 Manual call point DKM 3 3 bus capable 1 3 2 1 2 4 7 mm 8 10 mm Wiring ...
Страница 6: ...in the display Change address with the two gray buttons Dots blink behind the figures while the address is being changed Save address with the colored button The blinking dots behind the figures vanish Unplug detector and switch off programming tool Potential fault messages on programming tool bAt Replace battery battery service life approx 3 000 programming cycles E0 Incorrect programming attempt...