Oppermann Regelgeräte DKM 3.3 Скачать руководство пользователя страница 1

  

Fire Protection  |  Data sheet No. 49103  |  Version 01-2016  | 

1

 | 

6

Manual call point DKM 3.3 – bus capable for STG 1.2

Technical Data

Power supply:

 

17 – 31 V DC 

 

from STG 1.2 via system bus

Power consumption:

 

Switch-off current 100 µ A

 

Standby current 250 µ A

 

Alarm current 620 µ A

 

Short-circuit current 8 mA

 

Rated continuous current 1 A

LED displays:
Alarm:

 

red LED on

Short-circuit:

 

yellow LED on

Alarm- + short-circuit:

 

yellow LED on

Alarm- + fault signal:

 

via bus on STG 1.2

Rated operating 
temperature:

 

-10 – + 50 °C

Rated storage 
temperature:

 

-30 °C – + 60 °C

Rated humidity:

 

95 % RH (at 40 °C)

Gehäuse:

 

ABS plastic

Dimensions  (L x W x D):

 

135 x 135 x 37 mm

Weight:

 

approx. 0.3 kg

Protection type:

 

IP52 / IP54 (with gasket)

Connections:

 

6 x screw terminals 1.5 mm²

Colors:

 

blue, yellow, red

• 

For Oppermann control unit STG 1.2

• 

Power supply and communication via safety 

ringbus

• 

Housings in different colors

• 

LED display on alarm (red) and short circuit 

(yellow)

• 

Custom labeling on request

• 

Installation-friendly housing

• 

Straightforward installation 

Product description / Function

The DKM communicates with the STG via the safety-monitored 
system ringbus. The detectors forward fault and alarm mes-
sages to the STG and indicated on a display. A technician or 
building manager can therefore see all connected detectors at a 
glance. Important .

Note:

 Please also note separate specification sheets for STG 1.2.

The manual call point consists of the plastic housing and door. 
It contains the circuit board with terminals, trigger mechanism, 
and push-button. The replaceable standardized thin glass 
pane in a lockable door (protected by a standardized lock) is 
a safeguard against unintended triggering. In the event of an 
alarm, the glass pane is easily broken and the pushbutton can 
be pressed without interference. A special retainer keeps the 
button in the pressed position. The manually actuated retainer 
lever is used to release the push button. The particularly low-
profile configuration of the manual call point eliminates the 
need for in-wall installation. 

The detector has cable connection terminals on top and on the 
bottom. An opening can be punched out on the rear face of 
the detector for installation on an in-wall cup. In the event of 
an alarm, the glass pane (2) is punched in first, and the push-
button (3) is then pressed deeply. This actuates the micro-
switch to trigger the alarm; display LED (4) lights up. A locking 
mechanism retains the engaged push-button. The engaged 
push-button is reset by manually actuating the reset lever (5) or 
by opening the detector door (1). The alarm is reset and the LED 
(4) goes dark. The alarm must also be reset on the STG.

2

4

1

5

2

3

3

1

2

4

1

5

2

3

3

1

Содержание DKM 3.3

Страница 1: ...anager can therefore see all connected detectors at a glance Important Note Please also note separate specification sheets for STG 1 2 The manual call point consists of the plastic housing and door It contains the circuit board with terminals trigger mechanism and push button The replaceable standardized thin glass pane in a lockable door protected by a standardized lock is a safeguard against uni...

Страница 2: ... automatic fire detectors can be connected to a primary cable The test detector can be used on primary cables together with auto matic fire detectors It is connected at the electrical end of the primary cable max 1 test detector per primary cable The distance between non automatic fire detectors should be no more than 100 meters iaw DIN 14 675 and 80 meters iaw VdS Non automatic fire detectors sho...

Страница 3: ... point DKM 3 3 bus capable Installation dimensions Space requirements toward the right to open the detector 60 mm 135 mm 37 mm 135 mm 17 mm 13 mm ca 35 mm Surface mounted installation remove circuit board first In wall installation 3 4 4 x 40 mm 2x S 5 2x 5 approx 35mm ...

Страница 4: ...ry The assigned default address is 1 On request Oppermann can configure the detectors with custom BUS addresses indicate in your order The positioning of addressed DKMs in the ringbus is arbitrary A fault alarm is triggered if the same detector address is assigned twice on the ringbus If the detector address is changed the detector must be reregistered with the STG in service mode For connection t...

Страница 5: ... Fire Protection Data sheet No 49103 Version 01 2016 5 6 Manual call point DKM 3 3 bus capable 1 3 2 1 2 4 7 mm 8 10 mm Wiring ...

Страница 6: ...in the display Change address with the two gray buttons Dots blink behind the figures while the address is being changed Save address with the colored button The blinking dots behind the figures vanish Unplug detector and switch off programming tool Potential fault messages on programming tool bAt Replace battery battery service life approx 3 000 programming cycles E0 Incorrect programming attempt...