                                                                  CHECK THERMOSTAT OPERATION 

Switch on the thermostat 

Fan operation   

1. 

Push fan button, display will show 

 

   

and Auto separately means fan rotate in HI 

MED LOW or AUTO speed.   

2. 

If you select AUTO speed, fan operation will 

change speed according to the difference 

between the room temperature and set 

temperature. If room temperature is 3

 

higher than setting temperature in cooling 

or3

 lower than setting temperature in 

Heating. Fan will run in HI speed. If room 

temperature is 2

- 3

 higher than setting 

temperature in cooling or 2

-3

 lower than 

setting temperature in Heating. Fan will run 

in Medium speed. If room temperature is 

0

-2

 higher than setting temperature in 

cooling or 0

-2

 lower than set

ting 

temperature in Heating. Fan will run in Low 

speed. 

Heat system operation

 

1. 

Press system switch to heat mode ( 

    ) 

2. Press 

” to adjust the thermostat setting 

above the room temperature. The heating 

system should start to operate. 

3. Press 

“ to adjust the thermostat setting 

below the room temperature. The heating 

system should stop operating. 

Cooling system operation

 

1. 

Press system switch to cool mode ( 

    ) 

2. Press 

“ to adjust thermostat setting below 

room temperature. The cooling system 

should start to operate.     

3. 

Press “

” to adjust temperature setting 

above room temperature. The cooling 

system should stop operating 

 

 

Energy Saving Mode 

Energy Saving mode is activated by a special input from a card key, occupancy switch or window 

contact switch. If the signal via input terminals 10 and 11 is calling for energy saving mode. Then the 

thermostat will control to user/installer defined setback setpoints for increased energy savings. The 

display will show                symbol to indicate when this mode is active. The energy setpoint can be 

change in configuration item No.7 and No. 8.    Factory default setting for heating is 18

, for cooling is 

25

.  

For example, if the user setpoint is 21

 and the energy Savings Mode setpoint for cooling 

(unoccupied cooling setpoint) has been set to 28

, then the thermostat will control to 28

 when the 

input signal activated the Energy Saving mode. . 

The energy saving mode input can be configured within the configuration menu 9 to be activated 

either a short circuit (default) or open circuit signals.   

 

 

 

 

CONFIGURATION  

11

10

CARD KEY

The configuration menu allows you to set certain thermostat operating characteristics to your system or 

personal requirements. Switch off the thermostat and hold the sleep operation Button 

 for over 3 second till 

power on again means you have entered the first configuration menu item. There are 6 menu items. Press 

button 

 to change to the next item. To exit the menu and return to the normal operation, switch off the 

thermostat and switch it on

 aga

in. If no keys are pressed within 20 seconds the thermostat will be switched off. 

 