I N S T A L L A T I O N  

39 / 90 

 

ZE800_manual_ger_eng_it_V1.0.2.doc

 .............................................................................. 

R. Kistler

 

3.3  Checking the accessories 

RS232 interface cable 

USB interface cable 

10A low-heat devices power 
cord extension 

DataWatch software 

Operating instructions 

Table 1: Package 

3.4  Commissioning 

 

NOTE 

Make sure that the total  nominal power of all connected de-
vices does not exceed the capacity of the UPS system. 

 

1.  Connect  the  consumers  to  the  UPS  system  without  switching 

them on. 

2.  Plug  the  power  cable  of  the  UPS  system  into  a  socket.  The 

display of the UPS system lights up. 

3.  Keep the button 

 on the UPS system pressed for at least two 

seconds. 

4.  If  the  display 

  lights  up,  remedy  all  warning  messages  and 

restart the UPS system, if necessary. (See 

Troubleshooting

.) 

5.  Ensure  that  the  display 

  lights  up  continuously.  This  indi-

cates that the UPS system is working in normal mode and the 
consumers are being provided with power. 

Содержание ZINTO E 800

Страница 1: ...talien Schweiz ONLINE USV Systeme AG Luise Ullrich Str 8 D 82031 Grünwald Phone 49 89 2423990 10 Fax 49 89 2423990 20 www online usv de ONLINE UPS Systems S r l Via Gilera Ferruccio 110 I 20862 Arcore MB Phone 39 039 2051444 Fax 39 039 2051435 www online ups it ONLINE USV Systeme AG Eigenheimstraße 11 CH 8304 Wallisellen Zürich Phone 41 44 9452829 Fax 41 44 9453288 www online usv ch ...

Страница 2: ...2 90 ZE800_manual_ger_eng_it_V1 0 2 doc R Kistler ...

Страница 3: ... Starten und Abschalten 14 5 Kommunikation 16 5 1 RS232 und USB Schnittstelle 16 5 2 DataWatch Software 17 5 3 USB für HID Power Devices 17 6 Wartung 18 6 1 Pflege und Wartung 18 6 2 Lagerung 18 6 3 Zeitpunkt für den Batteriewechsel 18 6 4 Batteriewechsel 19 6 5 Entsorgen der Altbatterien oder der USV Anlage 22 7 Fehlerbehebung 23 7 1 Warnmeldungen 23 7 2 Allgemeine Fehler 24 7 3 Stummschalten des...

Страница 4: ...ngen 12 Abbildung 6 RS232 und USB Schnittstelle 16 Abbildung 7 Entfernen der Frontblende 20 Abbildung 8 Trennen der Batterie Steckverbindung 21 Abbildung 9 Entfernen der Metall Schutzabdeckung 21 Abbildung 10 Entnahme des Batterieeinschubes 21 Abbildung 11 Rückansicht 27 Tabellenverzeichnis Tabelle 1 Lieferumfang 9 Tabelle 2 Warnmeldungen 23 Tabelle 3 Allgemeine Fehler 24 Tabelle 4 Spezifikation 2...

Страница 5: ...n aus wenn man es am we nigsten erwartet Auch kann die Qualität der Stromversorgung oft er heblichen Schwankungen unterliegen Netzprobleme können dazu führen dass kritische Daten zerstört werden ungesicherte Daten verloren gehen und Hardware beschädigt wird Teure Reparaturen und Ausfallstunden sind die Folge Ob preissensitiver Einstiegsserver oder Highend PC Telefonanlage Netzwerkperipherie oder N...

Страница 6: ... Leises Betriebsgeräusch NAS Kompatibilität Perfekte Sinus Ausgangsspannung Wirkungsgrad von 95 EBM Ladetechnologie für 72 Monate Batterielebenserwar tung Hot Swap Batterie Wechsel im laufenden Betrieb ohne Ab schalten der Verbraucher RS 232 und USB Schnittstelle Kaltstartfunktion 2 Jahre Garantie inkl Batterie Abbildung 2 ZINTO E 800 ...

Страница 7: ...uden mit kontrollierter Temperatur und Luftfeuchtigkeit installiert wer den in denen keine leitenden Schmutzstoffe vorhanden sind Die Umgebungstemperatur darf 40 C nicht übersteigen Die USV Anlage darf nicht in der Nähe von Wasser oder in ex trem hoher Luftfeuchtigkeit 95 betrieben werden Vergewissern Sie sich vor dem Transport der USV Anlage dass die USV Anlage von der Stromversorgung getrennt un...

Страница 8: ...s zu Kondensatbildung innerhalb und außerhalb des Gehäuses kommen Installieren Sie die USV Anlage nur wenn Innen und Außenseite vollständig trocken sind Gefahr eines elektrischen Schlages Die USV Anlage hat ein hohes Gewicht siehe Technische Daten Vorsicht beim Auspacken und Transportieren der USV HINWEIS Bewegen und öffnen Sie die verpackte USV Anlage vorsich tig Lassen Sie die Komponenten in der...

Страница 9: ...hreitet 1 Verbinden Sie die Verbraucher mit der USV Anlage ohne die Verbraucher einzuschalten 2 Stecken Sie das Netzanschlusskabel für die USV Anlage in eine Steckdose Das Display der USV Anlage leuchtet auf 3 Halten Sie die Taste an der USV Anlage mindestens zwei Sekunden lang gedrückt 4 Falls die Anzeige aufleuchtet beheben Sie alle Warnmel dungen und starten Sie die USV Anlage ggfs neu siehe Fe...

Страница 10: ...ngangsfrequenz gesetzt die automatische Er kennung ist standardmäßig aktiviert 6 Schalten Sie die Verbraucher der Reihe nach ein HINWEIS Die internen Batterien lassen sich in weniger als drei Stun den auf 90 ihrer Kapazität aufladen ONLINE empfiehlt die Batterien nach der Installation oder nach längerer Lagerung 48 Stunden lang aufzuladen ...

Страница 11: ...Informationen über die Verwendung der ZINTO E wie Nutzung des Bedienfeldes an der Vorderseite Einstel lungen Betriebsarten sowie Starten und Abschalten der USV Anlage 4 1 Bedienfeld Abbildung 3 Bedienfeld 4 2 Display Abbildung 4 Display HINWEIS Die Anzeige schaltet nach drei Minuten ohne Betätigung ab ...

Страница 12: ... das Menü Alarm 9 Sekunden lang für das Menü Sensitivity Warten Sie bis das Display zu blinken aufhört um Ihre Auswahl ab zuspeichern Abbildung 5 Einstellungen HINWEIS 1 Im sensibilitätsreduzierten Modus Lo erlaubt die USV Anlage stärkere Stromschwankungen und schaltet weniger häufig auf Batteriebetrieb um Wenn die angeschlossene Last auf Stromschwankungen empfindlich reagiert sollte die Sensibili...

Страница 13: ...eschlossenen Verbraucher werden über die Batterie mit Strom versorgt Ist der Batterieladezustand im Batteriebetrieb niedrig ertönt der Alarm alle drei Sekunden Die verbleibende Überbrückungszeit ist gering Schließen Sie alle Anwendungen da die automatische Ab schaltung der USV Anlage kurz bevorsteht Ist der Batterieladezustand im Batteriebetrieb erschöpft schaltet sich die USV Anlage ab Alle Anzei...

Страница 14: ...ehend leuchtet Die USV Anlage arbeitet im Normalbetrieb und ver sorgt die Verbraucher mit Strom Starten im Batteriebetrieb HINWEIS Um die Ausgangsfrequenz von 50 oder 60Hz zu aktivieren muss die USV Anlage vor der erstmaligen Verwendung des Batteriebetriebs mindestens einmal vom Netz versorgt und gestartet worden sein 1 Halten Sie die Taste an der USV Anlage gedrückt bis das Display aufleuchtet Di...

Страница 15: ...es Signal Die USV Anlage wechselt in den Standby Betrieb und die Anzeige erlischt HINWEIS Wird die Taste nach weniger als drei Sekunden losgelas sen so kehrt die USV Anlage wieder zu ihrer vorherigen Be triebsart zurück 2 Ziehen Sie das Netzanschlusskabel der USV Anlage aus der Steckdose Das Display der USV Anlage erlischt nach kurzer Zeit und die USV Anlage schaltet sich komplett aus ...

Страница 16: ...atenkabels Kabel im Lieferumfang an die RS 232 oder USB Schnittstelle der USV Anlage an siehe Abbildung 6 HINWEIS RS232 und USB Schnittstelle können nicht gleichzeitig ver wendet werden Danach kann die USV Anlage Daten über die DataWatch Software siehe DataWatch Software austauschen Mittels USB Protokoll besteht auch die Möglichkeit des direkten Datenaustausch ohne Softwareinstallation siehe USB f...

Страница 17: ...r Anwendungen und dem geordneten Herunter fahren des gesamten Systems mittels frei konfigurierbarer Shut downroutine Darüber hinaus verfügt DataWatch über ein umfangrei ches Messaging System zeitgesteuerte Testroutinen sowie eine Er eignisprotokollierung DataWatch unterstützt alle aktuellen Betriebssysteme Als Client Server Anwendung arbeitet DataWatch in Netzwerken und auf lokalen Workstations Mi...

Страница 18: ...it und Umgebungstemperatur Nach Ablauf der zu erwartenden Lebensdauer haben weiter verwendete Batte rien häufig deutlich verringerte Laufzeiten Tauschen Sie die Batterien rechtzeitig aus damit die Anlage immer mit optima ler Leistung läuft 6 2 Lagerung Falls Sie die USV Anlage über längere Zeit lagern laden Sie die Bat terie alle sechs Monate auf indem Sie die USV Anlage an das Ver sorgungsnetz an...

Страница 19: ...traut ist Halten Sie unbefugtes Personal von den Batterien fern Batterien bergen das Risiko eines elektrischen Schlags oder einer Verletzung durch hohe Kurzschlussströme Halten Sie folgende Sicherheitsvorkehrungen ein o Nehmen Sie Uhren Schmuck und andere Metallgegen stände ab o Verwenden Sie nur Werkzeug mit isolierten Griffen o Legen Sie Werkzeuge oder Metallteile nicht auf den Bat terien ab Die...

Страница 20: ...hren Die internen Batterien der USV Anlage haben ein hohes Gewicht Beim Umgang mit den schweren Batterien ist Vor sicht geboten Die Batterien befinden sich hinter der Frontblende der USV Anlage Die internen Batterien sind wegen der besseren Handhabung zu sammen verpackt 1 Entfernen Sie die Frontblende nach vorne siehe Abbildung 7 Abbildung 7 Entfernen der Frontblende HINWEIS Ein Flachbandkabel ver...

Страница 21: ...eln siehe Abbildung 8 Abbildung 8 Trennen der Batterie Steckverbindung 3 Entfernen Sie die Me tall Schutzabdeckung die mit einer Schraube gesichert ist siehe Abbildung 9 Abbildung 9 Entfernen der Metall Schutzabdeckung 4 Ziehen Sie den Batte rieeinschub vorsichtig am Griff heraus siehe Abbildung 10 Abbildung 10 Entnahme des Batterieeinschubes ...

Страница 22: ...Personen führen Führen Sie das Kabel der Batterien schnell und kräftig in die Batterie Steckverbindung der USV Anlage ein 6 5 Entsorgen der Altbatterien oder der USV Anlage Erkundigen Sie sich vor Ort bei einer Recycling Stelle wie die Altbat terie oder die USV Anlage ordnungsgemäß entsorgt werden können Altbatterien können auch kostenlos bei ONLINE entsorgt werden Bitte kontaktieren Sie hierzu de...

Страница 23: ...ufgetre ten Überprüfen Sie die angeschlosse nen Verbraucher auf einen Defekt Wenden Sie sich an den Support Batteriestörung Die Batterien in der USV Anlage sind nicht ange schlossen Vergewissern Sie sich dass die Bat terien ordnungsgemäß angeschlos sen sind Wenden Sie sich an den Support Die Lebensdauer der Batte rie ist abgelaufen Tauschen Sie die Batterien Lüfterstörung Der Lüfter der USV Anlage...

Страница 24: ...en lang ge drückt bis auf dem Anzeigefeld Normalbetrieb angezeigt wird Die USV Anlage wird nicht gestar tet Das Stromkabel ist nicht richtig angeschlossen Prüfen Sie die Anschlüsse des Netzkabels Die USV Anlage läuft im Normalbe trieb aber einige oder alle Verbrau cher sind nicht ein geschaltet Die Verbraucher sind nicht richtig an die USV Anlage angeschlossen Überprüfen Sie ob die Verbraucher mit...

Страница 25: ...ch dem Kauf Bei ONLINE werden umfassende Support und Serviceleistungen groß geschrieben Direkte Beratung und Support kostenlos unter Software Hotline 49 89 242 39 90 13 Hardware Hotline 49 89 242 39 90 18 Kostenloser 24h Vorabaustausch Interaktiver USV Konfigurator im Internet oder als App 2 Jahre Vollgarantie optionale Verlängerung Unbürokratische 14 Tage Geld zurück Garantie Hohe Warenverfügbark...

Страница 26: ...Batteriebetrieb 50 60Hz 0 1Hz Anschlüsse Eingang 1x IEC C14 10A Ausgänge 8x IEC C13 10A Batterien Typ Überbrückungszeiten bei 50 bzw 100 Last und pf 0 7 18 8min Batterietyp 2x 12V 9Ah Ausführung Versiegelt wartungsfrei ventilgeregelt Gitter Vlies Lebensdauer 3 5 Jahre gemäß EUROBAT Batterie Management EBM Automatischer Batterietest Tiefentladungs schutz Kommunikation 1 USB und 1 RS 232 Schnittstel...

Страница 27: ...T E C H N I S C H E D A T E N 27 90 ZE800_manual_ger_eng_it_V1 0 2 doc R Kistler 8 2 Rückansicht Beschreibung der Kommunikationsfunktionen siehe Abbildung 6 Abbildung 11 Rückansicht ...

Страница 28: ...T E C H N I S C H E D A T E N 28 90 ZE800_manual_ger_eng_it_V1 0 2 doc R Kistler 8 3 CE Bestätigung ...

Страница 29: ...on hierin vorgesehenen Ausnahmen abgesehen übernimmt ONLINE keinerlei ausdrückliche oder stillschweigende Garantie ein schließlich der Zusicherung handelsüblicher Qualität oder der Eig nung für einen bestimmten Zweck In einigen Gerichtsbarkeiten ist die Einschränkung oder der Ausschluss stillschweigender Garantien untersagt so dass die vorstehenden Einschränkungen oder Aus schlüsse für den Käufer ...

Страница 30: ...30 90 ZE800_manual_ger_eng_it_V1 0 2 doc R Kistler ...

Страница 31: ...Switzerland ONLINE USV Systeme AG Luise Ullrich Str 8 D 82031 Grünwald Phone 49 89 2423990 10 Fax 49 89 2423990 20 www online usv de ONLINE UPS Systems S r l Via Gilera Ferruccio 110 I 20862 Arcore MB Phone 39 039 2051444 Fax 39 039 2051435 www online ups it ONLINE USV Systeme AG Eigenheimstraße 11 CH 8304 Wallisellen Zürich Phone 41 44 9452829 Fax 41 44 9453288 www online usv de ...

Страница 32: ...32 90 ZE800_manual_ger_eng_it_V1 0 2 doc R Kistler ...

Страница 33: ...ating states 43 4 5 Startup and shutdown 44 5 Communication 46 5 1 RS232 and USB interface 46 5 2 DataWatch software 47 5 3 USB for HID power device 47 6 Maintenance 48 6 1 Care and maintenance 48 6 2 Storage 48 6 3 Proper time to change the battery 48 6 4 Battery change 49 6 5 Disposing of old batteries or the UPS system 52 7 Troubleshooting 53 7 1 Warning messages 53 7 2 General faults 54 7 3 Mu...

Страница 34: ...gure 5 Settings 42 Figure 6 RS232 and USB interface 46 Figure 7 Removing the front cover 50 Figure 8 Disconnecting the battery plug connection 51 Figure 9 Removing the protective metal cover 51 Figure 10 Removing the battery module insert 51 Figure 11 Rear view 57 List of tables Table 1 Package 39 Table 2 Warning messages 53 Table 3 General faults 54 Table 4 Specification 56 ...

Страница 35: ...r mains often fails when least expected The quality of the power supply is also often subject to considerable fluctuations Mains problems can lead to critical data being destroyed unsecured data being lost and hardware being damaged Expensive repairs and downtimes are the result Whether expensive entry servers or high end PCs telephone sys tems network periphery or NAS ZINTO E protect sensitive ap...

Страница 36: ... operating noise NAS compatibility Perfect sinusoidal output voltage 95 efficiency EBM charging technology for expected 72 month battery ser vice life Hot swap battery Change during operation without deactiva tion of the consumers RS 232 and USB interfaces Generator compatibility Cold start function 2 year guarantee including battery Figure 2 ZINTO E 800 ...

Страница 37: ... shock the UPS sys tem may only be installed in buildings with controlled tem perature and air humidity in which there are no conducting contaminants present The ambient temperature may not rise above 40 C The UPS system must not be operated near water or in extremely high humidity 95 Make sure that the UPS system is switched off and discon nected from the power supply before transporting the UPS ...

Страница 38: ...ent tempera tures condensation may form on the outside and inside of the housing Install the UPS system only when the inside and outside are completely dry risk of an electric shock The UPS system is heavy see Technical Data Use caution when unpacking and transporting the UPS system NOTE Move and open the packaged UPS system carefully Leave the components in the packaging until these are installed...

Страница 39: ...s not exceed the capacity of the UPS system 1 Connect the consumers to the UPS system without switching them on 2 Plug the power cable of the UPS system into a socket The display of the UPS system lights up 3 Keep the button on the UPS system pressed for at least two seconds 4 If the display lights up remedy all warning messages and restart the UPS system if necessary See Troubleshooting 5 Ensure ...

Страница 40: ...is set to the value of the input frequency the automatic detection is enabled by default 6 Switch on the consumers one after the other NOTE The internal batteries will charge up to 90 of their capacity in less than three hours ONLINE recommends charging the batteries for 48 hours after installation or after a longer peri od of storage ...

Страница 41: ...doc R Kistler 4 Operation This section contains information on the use of ZINTO E like the use of the front control panel settings operating modes and starting and stopping the UPS system 4 1 Control panel Figure 3 Control panel 4 2 Display Figure 4 Display ...

Страница 42: ...enu 7 seconds long for the Alarm menu 9 seconds long for the Sensitivity menu Wait until the display stops flashing to save your selection Figure 5 Settings NOTE 1 In sensitivity reduced mode Lo the UPS system permits stronger fluctuations and switches to battery operation less often If the connected load reacts sensitively to current fluc tuation the sensitivity should be left in standard mode St...

Страница 43: ...ery ten seconds The connected consumers are supplied with power through the battery If the battery charge state is low during battery operation the alarm sounds every three seconds The remaining delay time is brief Close all applications since the automatic deactivation of the UPS system is about to take place If the battery charge state is empty during battery operation the UPS system switches of...

Страница 44: ...s up continuously The UPS system works in normal mode and supplies the consumers with power Startup in battery mode NOTE To activate the output frequency of 50 or 60Hz the UPS sys tem must be supplied from the power supply and started at least once before the first use of the battery mode 1 Keep the button on the UPS system pressed until the dis play lights up The UPS system runs through the self ...

Страница 45: ...ts a brief acoustic signal The UPS sys tem switches to standby mode and the display goes out NOTE If the button is released after less than 3 seconds the UPS system will return to its previous operating mode 2 Plug the power cable of the UPS system into a socket The display of the UPS system goes out after a short time and the UPS system shuts down completely ...

Страница 46: ...S232 or USB interface of the UPS system using a suitable data cable included in delivery see Figure 6 NOTE The RS232 and USB interfaces cannot be used at the same time Afterwards the UPS system can exchange data via the DataWatch software see DataWatch software Using the USB protocol it is also possible to exchange data directly without installing software see USB for HID power device Figure 6 RS2...

Страница 47: ...he closing of running ap plications and the orderly shutdown of the entire system by means of freely configurable shutdown routine DataWatch also includes a comprehensive messaging system scheduled test routines and event logging DataWatch supports all current operating systems As client server application DataWatch works in networks and on lo cal workstations Using the optional RCCMD agent Remote...

Страница 48: ...ding on the frequency of use and ambient temperature After expira tion of the expected service life batteries which continue to be used frequently have reduced running times Exchange the batteries regularly so that the system is always running at optimum performance 6 2 Storage If you store the UPS system over a longer period of time charge the batteries every six months by connecting the UPS syst...

Страница 49: ...batteries and un derstands the necessary safety precautions Keep unauthor ised personnel away from batteries Batteries can pose a risk of electric shock or injury due to high short circuit currents Comply with the following safety precautions o Remove watches jewellery and other metal objects from your body o Use only tools with insulated grips and handles o Do not place tools or metal parts on to...

Страница 50: ...erious injuries The internal batteries of the UPS system are heavy Use caution when handling the heavy batteries The batteries are located behind the front cover of the UPS system For better handling the internal batteries are packaged together 1 Remove the front cover towards the front see Figure 7 Figure 7 Removing the front cover NOTE A ribbon cable connects the LCD display and the control pane...

Страница 51: ...u does not pull on the cable see Figure 8 Figure 8 Disconnecting the battery plug con nection 3 Remove the protective metal cover which is secured with a screw see Figure 9 Figure 9 Removing the protective metal cover 4 Carefully pull out the battery module insert by the handle see Figure 10 Figure 10 Removing the battery module insert ...

Страница 52: ...and does not pose a hazard to people Quickly and firmly insert the cable of the batteries into the battery plug connection of the UPS system 6 5 Disposing of old batteries or the UPS system Contact the local recycling centre for information on disposing of the old batteries or UPS system properly You can also dispose of old batteries at ONLINE at no cost Please contact support for this option see ...

Страница 53: ...ted load Short circuit A short circuit has occurred Check the connected consumer for defects Please contact support Battery fault The batteries in the UPS system are not connected Make sure that the batteries are properly connected Please contact support The service life of the batter ies has expired Exchange the batteries Fan fault The fan of the UPS system has a fault Make sure that no objects a...

Страница 54: ...or at least two sec onds until normal mode is indicated on the display The UPS system is not started The power cable is not con nected correctly Check the connections of the mains cable The UPS system runs in normal mode however several or all con sumers are not switched on The consumers are not properly connected to the UPS system Check whether the consumers are connected with the connections of ...

Страница 55: ...e At ONLINE comprehensive support and service solutions are our top priority Direct consulting and support free of cost under Software hotline 49 89 242 39 90 13 Hardware hotline 49 89 242 39 90 18 Free 24 hour advanced replacement Interactive UPS configurator on the Internet or as app 2 years factory warrantee optional extension Hassel free 14 day money back guarantee High availability of goods a...

Страница 56: ...z 5Hz Battery mode 50 60Hz 0 1Hz Connections Line input 1x IEC C14 10A Line outputs 8x IEC C13 10A Batteries Typ delay times at 50 or 100 load and pf 0 7 18 8min Battery type 2x 12V 9Ah Design Sealed maintenance free valve regulated grid fabric Lifespan 3 5 years according to EUROBAT Battery management EBM automatic battery test excessive discharge pro tection Communication 1 USB and 1 RS232 inter...

Страница 57: ...T E C H N I C A L D A T A 57 90 ZE800_manual_ger_eng_it_V1 0 2 doc R Kistler 8 2 Rear view Description of the communication functions see Figure 6 Figure 11 Rear view ...

Страница 58: ...T E C H N I C A L D A T A 58 90 ZE800_manual_ger_eng_it_V1 0 2 doc R Kistler 8 3 CE conformity ...

Страница 59: ...en changed or modified in any way Save where explicitly provided otherwise ONLINE does not make any warranty express or implied including warranties as to quality or suitability for a specific purpose The laws of some jurisdictions do not allow the exclusion of implied warranties or limitations so that the existing restrictions or exclusions may possibly not apply to the purchaser Except as may be...

Страница 60: ...60 90 ZE800_manual_ger_eng_it_V1 0 2 doc R Kistler ...

Страница 61: ...talia Svizzera ONLINE USV Systeme AG Luise Ullrich Str 8 D 82031 Grünwald Phone 49 89 2423990 10 Fax 49 89 2423990 20 www online usv de ONLINE UPS Systems S r l Via Gilera Ferruccio 110 I 20862 Arcore MB Telefono 39 039 2051444 Fax 39 039 2051435 www online ups it ONLINE USV Systeme AG Eigenheimstraße 11 CH 8304 Wallisellen Zürich Phone 41 44 9452829 Fax 41 44 9453288 www online usv ch ...

Страница 62: ...62 90 ZE800_manual_ger_eng_it_V1 0 2 doc R Kistler ...

Страница 63: ... 5 1 Interfaccia RS232 e interfaccia USB 76 5 2 Software DataWatch 77 5 3 USB per HID Power Devices 77 6 Manutenzione 78 6 1 Cura e manutenzione dell UPS e delle batterie 78 6 2 Immagazzinamento dei sistemi UPS delle batterie 78 6 3 Sostituzione delle batterie 78 6 4 Sostituzione delle batterie 79 6 5 Smaltimento delle batterie vecchie o dell UPS 82 7 Risoluzione dei guasti 83 7 1 Messaggi di avve...

Страница 64: ...RS232 e interfaccia USB 76 Figura 7 Smontaggio del pannello frontale 80 Figura 8 Distacco del collegamento a innesto delle batterie 81 Figura 9 Smontaggio della copertura metallica di protezione 81 Figura 10 Estrazione dell inserto batterie 81 Figura 11 Vista posteriore 87 Indice delle tabelle Tabella 1 Dotazione della fornitura 69 Tabella 2 Messaggi di avvertimento 83 Tabella 3 Guasti generali 84...

Страница 65: ...no meno se lo aspetta Anche la qualità dell alimentazione può essere soggetta a notevoli oscillazioni I problemi di rete possono causare la perdita dei dati e il danneggiamento dell hardware Le conseguenze sono costose riparazioni e ore di inattività Che si tratti di un costoso server d accesso o un PC high end un im pianto di telecomunicazione una periferia di rete o un dispositivo NAS ZINTO E pr...

Страница 66: ...NAS Tensione di uscita sinusoidale perfetta Rendimento del 95 Tecnologia di carica EBM per una durata prevista della batte ria di 72 mesi Batteria hot swap sostituzione durante il funzionamento sen za disinserire le utenze Interfaccia RS 232 e interfaccia USB Compatibilità generatore Funzione di avviamento a freddo 2 anni di garanzia batteria inclusa Figura 2 ZINTO E 800 ...

Страница 67: ...elettrica l UPS può essere installato solo in edifici a tempe ratura e umidità controllate privi di sostanze conduttive e in quinanti La temperatura ambiente non deve essere superio re a 40 C L UPS non deve essere azionato in prossimità di acqua o in presenza di umidità atmosferica estremamente elevata 95 Prima di trasportare l UPS assicurarsi che questo sia discon nesso dall alimentazione elettri...

Страница 68: ...rodotti saranno considerati definitivamente accettati e conformi a quanto richiesto nell ordine Conservare i car toni di trasporto e il materiale d imballaggio per l eventuale reso in caso di guasto o non conformità 3 2 Disimballaggio dell UPS ATTENZIONE Se l UPS viene disimballato in presenza di basse temperatu re ambiente all interno e all esterno dell apparecchio può formarsi della condensa Ins...

Страница 69: ...nuale dell utente 1 Tabella 1 Dotazione della fornitura 3 4 Messa in funzione AVVERTENZA Assicurarsi che la potenza nominale complessiva di tutti gli apparecchi collegati non superi la capacità massima dell UPS 1 Collegare le utenze al sistema UPS senza attivarle 2 Collegare presa di corrente Il display dell UPS si accende il cavo di allacciamento alla rete dell UPS in una 3 Premere il tasto del s...

Страница 70: ...ul va lore della frequenza d ingresso il rilevamento automatico è attivato di default 6 Attivare le utenze una dopo l altra AVVERTENZA Le batterie interne si ricaricano in meno di tre ore fino al 90 della loro capacità ONLINE consiglia di ricaricare le batterie per 48 ore dopo l installazione o dopo un lungo periodo di immagazzinamento ...

Страница 71: ...afo sono contenute informazioni sull utilizzo di ZINTO E come l uso del quadro di comando sul lato frontale le mo dalità di funzionamento e l avvio e lo spegnimento dell UPS 4 1 Quadro di comando Figura 3 Quadro di comando 4 2 Display Figura 4 Display AVVERTENZA Il display si spegne dopo tre minuti di inattività ...

Страница 72: ...u Alarm Premendo per 9 secondi si arriva al menu Sensitivity Attendere che il display smetta di lampeggiare per memorizzare la selezione Figura 5 Impostazioni AVVERTENZA 1 Nella modalità a sensibilità ridotta Lo il sistema UPS permette oscillazioni di corrente più alte e passa con minor frequenza al funzionamento a batteria Se il carico collegato reagisce in modo sensibile alle oscillazioni di cor...

Страница 73: ...cende il simbolo e l allarme suona ogni dieci secondi Le utenze collegate vengono alimentate con corrente mediante la batteria Se nel funzionamento a batteria la carica della batteria è bassa l al larme suona ogni tre secondi Il tempo restante di autonomia è mi nimo Chiudere tutte le applicazioni perché è imminente lo spegni mento automatico dell UPS Se nel funzionamento a batteria la batteria è s...

Страница 74: ...lo sia sempre acceso L UPS lavora nella modalità normale e alimenta le utenze con corrente Avvio dell UPS in modalità a batteria AVVERTENZA Per attivare la frequenza in uscita di 50 o 60Hz è necessario che il sistema UPS sia stato alimentato dalla rete e avviato almeno una volta prima di poter usare la modalità a batteria 1 Premere il tasto dell UPS finché il display si accenda L UPS esegue l auto...

Страница 75: ...te un breve segnale acustico commuta sulla mo dalità Standby e il simbolo si spegne AVVERTENZA Se il tasto viene rilasciato dopo meno di tre secondi l UPS torna alla modalità d esercizio precedente 2 Staccare il cavo di collegamento alla rete dell UPS dalla presa di corrente Il display dell UPS si spegne dopo breve tempo e l UPS si spegne completamente ...

Страница 76: ...municazione dell UPS me diante un cavo dati idoneo cavo fornito in dotazione vedi Figura 6 AVVERTENZA Non è possibile utilizzare contemporaneamente le interfacce RS232 e USB Successivamente l UPS può scambiare dati tramite il software Da taWatch vedi Software DataWatch Con il protocollo USB è anche possibile lo scambio di dati diretto senza installazione di software vedi USB per HID Power Device F...

Страница 77: ...zione e lo spegnimento ordinato dell intero sistema Questo avviene per mezzo di una routine di spegnimento li beramente configurabile Inoltre DataWatch dispone di un avanzato sistema di Messaging di routine di test temporizzate e di un sistema di registrazione degli eventii DataWatch supporta tutti gli attuali sistemi operativi In applicazioni client server DataWatch lavora in rete e su worksta ti...

Страница 78: ...la temperatura ambiente Trascorsa la durata prevista le batterie che continuano ad essere utilizzate han no spesso tempi di funzionamento notevolmente inferiori Sostituire le batterie in tempo utile affinché il sistema possa funzionare sempre con la potenza ottimale 6 2 Immagazzinamento dei sistemi UPS delle batterie Se l UPS viene immagazzinato per un periodo di tempo prolungato caricare la batte...

Страница 79: ...enere il perso nale non autorizzato lontano dalle batterie Le batterie presentano il rischio di una scossa elettrica o di lesioni dovute a elevate correnti di cortocircuito Osservare le seguenti misure di sicurezza o Rimuovere orologi gioielli e altri oggetti in metallo o Utilizzare solo utensili con impugnature isolate o Non appoggiare utensili o parti in metallo sulle batterie Le batterie devono...

Страница 80: ...esioni Le batterie interne dell UPS hanno un peso elevato Durante la manipolazione delle batterie pesanti prestare la massima cautela Le batterie si trovano dietro il pannello frontale dell UPS e sono as semblate insieme per una migliore maneggevolezza 1 Rimuovere in avanti il pannello frontale vedi Figura 7 Figura 7 Smontaggio del pannello frontale AVVERTENZA Un cavo piatto collega il campo di vi...

Страница 81: ... cavo vedi Figura 8 Figura 8 Distacco del collegamento a innesto delle batterie 3 Togliere la protezione metallica che è fissa ta con una vite vedi Figura 9 Figura 9 Smontaggio della copertura metallica di protezione 4 Estrarre con cautela l inserto batterie tiran dolo dall impugnatura vedi Figura 10 Figura 10 Estrazione dell inserto batterie ...

Страница 82: ...ie vecchie o dell UPS Informarsi presso il centro di riciclaggio o l impianto di smaltimento dei rifiuti speciali presente nella propria zona per lo smaltimento cor retto delle batterie vecchie o dell UPS Le batterie vecchie possono essere smaltite gratuitamente anche inviandole a proprio carico ad ONLINE Per un gruppo di batterie con peso totale superiore ai 100 Kg sarà possibile concordare diret...

Страница 83: ...Si è verificato un cortocircui to Controllare le utente collegate per individuare il guasto Contattare il Servizio Assistenza Anomalia batterie Le batterie non sono colle gate nell UPS Controllare che tutte le batterie sia no collegate correttamente Contattare il Servizio Assistenza La durata di vita della batte ria è scaduta Sostituire le batterie Anomalia ventola La ventola dell UPS non funziona...

Страница 84: ...o due se condi finché il quadro indichi la mo dalità di funzionamento normale L UPS non viene avviato Il cavo elettrico non è colle gato correttamente Controllare i collegamenti del cavo di rete L UPS funziona in modalità normale tuttavia alcune o tutte le utenze non sono attivate Le utenze non sono collega te correttamente all UPS Controllare che le utenze siano col legate agli attacchi dell UPS ...

Страница 85: ... l acquisto I servizi di supporto e assistenza di ONLINE sono noti e apprezzati per la loro eccellenza Consulenza e supporto diretti Gratuitamente alla hotline 39 800 211980 39 39 2051 444 Sostituzione anticipata gratuita entro 24 ore Configuratore UPS interattivo in Internet o come app Garanzia totale di 2 anni con possibilità di estensione Garanzia soddisfatti o rimborsati entro 30 giorni nessun...

Страница 86: ...Funzionamento a batteria 50 60Hz 0 1Hz Collegamenti Ingresso 1x IEC C14 10A Uscite 8x IEC C13 10A Batterie Autonomia con carico 50 100 e pf 0 7 18 8min Tipo di batterie 2x 12V 7Ah Versione Sigillata esente da manutenzione regolata mediante valvola AGM Durata 3 5 anni secondo EUROBAT Gestione batterie EBM test automatico delle batterie protezione da sca ricamento completo Comunicazione 1 interfacci...

Страница 87: ...D A T I T E C N I C I 87 90 ZE800_manual_ger_eng_it_V1 0 2 doc R Kistler 8 2 Vista posteriore dell UPS Descrizione delle funzioni di comunicazione vedi Figura 6 Figura 11 Vista posteriore ...

Страница 88: ...D A T I T E C N I C I 88 90 ZE800_manual_ger_eng_it_V1 0 2 doc R Kistler 8 3 Dichiarazione CE ...

Страница 89: ...alterazioni o modifiche di qualunque genere Fatte salve le eccezioni qui previste ONLINE non fornisce alcuna ul teriore garanzia esplicita o implicita comprese garanzia di commer ciabilità o idoneità per uno scopo particolare Alcuni ordinamenti giu ridici non consentono limitazioni o esclusioni delle garanzie implicite pertanto le suddette limitazioni o esclusioni potrebbero non essere pertinenti ...

Страница 90: ...90 90 ZE800_manual_ger_eng_it_V1 0 2 doc R Kistler ...

Отзывы: