D-1401 & D-1402 Portable Metering System Installation and Operation Guide • 03-17

 

7

 

 

2.3 

BASI C FLOW M EASUREM ENT 

 

1.  Turn the power switch (left) to “

ON”

 position. 

2.  Set the middle switch to “

AVG”

 and allow 45 seconds for the flow meter 

circuitry to stabilize. 

3.  Record the average reading in Hz on the display and refer to the laminated 

conversion chart to calculate the flow rate.  Please note that the frequency 
number displayed may vary rapidly (by as much as 10-15%) as a result of 
the actual flow conditions in the pipe.  

4.  Locate the pipe size being measured on the laminated conversion chart and 

determine the “ Z Factor”  for gallons per minute (or liters per minute) for 
that pipe size. 

5.  Then multiply the Z factor by the average reading in Hz from step 3 to 

obtain the flow rate in gallons per minute. 

 
 

2.4 

FLOW PROFI LI NG M EASUREM ENT 

 

D-1401 / D-1402 Systems: 
Significant information about the nature of flow across the entire pipe diameter 
can be obtained by taking flow measurements at incremental insertion depths. 
 
Depending on the pipe size to be measured, determine an appropriate 
measurement increment that will provide the required information.  (For 
example:  when measuring the flow profile of an 8-inch pipe, measurements 
may be made at 1 inch increments to provide the desired profile.) 
 
With the flow meter properly inserted in the pipe, loosen the hot tap adaptor 
lock nut and push the meter into the pipe until the end of the meter touches the 
far pipe wall.  Using this as a starting point, pull the meter back out by the 
desired increment of measurement and measure the flow rate.  Repeat this 
process until readings have been made across the entire interior diameter of the 
pipe. 
 
In large pipes where the flow meter is not long enough to touch the far pipe 
wall, measurements can be made using the near pipe wall as a starting point. 
Push the flow meter into the pipe just until a flow reading is obtained on the 
display. (For the  
D-1402 systems, the top turbine output can be observed to see when it clears 
the pipe wall and begins to spin.) Beginning at that point, start making 
measurements at the desired incremental insertion depths. 
 
D-1402 System Only: 

Содержание D-1401

Страница 1: ...Model D 1401 D 1402 PortableMeteringSystem Installation and Operation Guide 03 17 11451 Belcher Road South Largo FL 33773 Tel 1 727 447 6140 Fax 1 727 442 5699 www onicon com E mail sales onicon com ...

Страница 2: ...ismanual Servicerequirements Thisproduct containsalimited number of user serviceableparts Only qualified personnel should install or servicethisproduct Pleasedo not hesitateto contact ONICON for assistancein theunlikely event that this product requiresservice IMPORTANT NOTE Messagesidentified as Important Note contain information critical to theproper operation of themeter CAUTION Messagesidentifi...

Страница 3: ...0 SYSTEM OPERATION AND SET UP 6 2 1 System Operation 6 2 2 Initial System Set up 6 2 3 Basic Flow Measurement 7 2 4 Flow Profiling Measurement 7 2 5 System Storageand MaintenanceRecommendations 8 2 6 Flow Meter Information 9 3 0 INSTALLATION REMOVAL AND ADJUSTMENT 10 3 1 SiteSelection 10 3 2 Mechanical Installation 11 3 3 Insertion of theMeter 13 3 4 Removal of theMeter 14 CONDITIONSOF SALE 16 ...

Страница 4: ...402 PortableMetering System includesaF 1200 dual turbineflow meter and can beused to measure2 5 inch and larger pipesizes Theflow meter portion of thesystem istypically inserted into afilled and pressurized pipeviaan existing oneinch minimum diameter full port ball valve For pipesthat can beeasily drained beforeand after measurement theflow meter can beinserted into aoneinch minimum diameter outle...

Страница 5: ...display Carrying case Owner smanual Laminated conversion chart Serialized for thespecific F 1100 flow meter TheD 1402 PortableMetering System containsthefollowing components Model F 1200 Insertion TurbineFlow Meter Model D 1402 battery powered hand held display Carrying case Owner smanual Laminated conversion chart Serialized for thespecific F 1200 flow meter ...

Страница 6: ...theselection switcheson theDisplay Module Thisfrequency output isthen converted to gallonsper minute for thepipesizebeing measured viathelaminated conversion chart included with thesystem Pleasecontact Onicon to obtain conversion factorsfor any pipesizesnot listed on thechart or if you requirea flow rate unit of measureother than gallonsor liters 2 2 INTIAL SYSTEM SET UP 1 Insert theflow meter int...

Страница 7: ...asurementsat incremental insertion depths Depending on thepipesizeto bemeasured determinean appropriate measurement increment that will providetherequired information For example when measuring theflow profileof an 8 inch pipe measurements may bemadeat 1 inch incrementsto providethedesired profile With theflow meter properly inserted in thepipe loosen thehot tap adaptor lock nut and push themeter ...

Страница 8: ...easethespeed of rotation of oneof theturbinesand will havetheoppositeeffect on theother turbine 2 5 SYSTEM STORAGE AND MAINTENANCE RECOMMENDATION 1 Alwaysstorethesystem in itscarrying casewhen not in use 2 Beforelong term storageof thesystem blow all excesswater from theflow meter turbineassembly and wipetheflow meter stem assembly dry with a clean cloth Donot put any lubricantson theturbineassemb...

Страница 9: ...9 ONICON sD 1401 D 1402 Insertion TurbineFlow Meter measuresthe velocity of flowing liquidsby counting thefrequency at which thebladesof a rotating turbinepassafixed electrode Circuitry within theflow meter electronicsenclosurethen convertsthe rotational rateto afrequency output ...

Страница 10: ...heating coolingand fluid meteringfieldsshould attempt toinstall adjust or remove theflow meter Refer totheinstallation drawingsbeforeperformingany work on thesemeters 3 1 SITE SELECTION Theclearancerequired for installation istypically 30 36 from thepipewall to thenearest obstruction abovethevalveassembly Thisclearancedimension will increasewith large diameter pipes Theenvironment should befreeof ...

Страница 11: ... Hot Tap feature it must beinstalled through an isolation valve Thelocation must allow sufficient overhead clearancefor meter removal IMPORTANT A full 1 opening isrequired to clear theturbineassembly Makesurethat your valvesand fittingsarefull port and at least 1 in actual internal diameter Also notethat an oversized accessholecan causeundesirableturbulence ...

Страница 12: ...evalve without shutting down or draining thepipe SeeAppendix A for List of AvailableOnicon Installation HardwareKitsfor other typesof pipe materialsand applications After fitting thenecessary plumbing hardware flush theentiresystem so that it isfreeof flux solder and slag Prepareto install theflow meter by loosening theclamping nut and withdrawing theturbineassembly fully into thehot tap adapter N...

Страница 13: ...largeamountsof water Thehand effort required tohold the meter will be0 11 timesthepipepressure Begin by calculating theeffort that will berequired to hold themeter Establish adequatefooting for thistask taking extracaution when working from aladder or platform Usethefollowing formula E 0 11 x P Where E effort in pounds P system pressurein poundsper squareinch Example In a300 PSI system 33 poundsof...

Страница 14: ...eter limited for any reason DO NOT loosen the clamping nut SLOWLY loosen theposition clamping nut and carefully and slowly allow thepressureto forcethemeter out of thepipe Thisisnot at all difficult but you must not let go of themeter until it isfully withdrawn into the hot tap adapter After themeter iscompletely withdrawn you may closetheisolation ball valve Themain causeof damageto meterscomesfr...

Страница 15: ...402 Portable Metering System Installation and Operation Guide 03 17 15 CAUTION In hot water systems even a small amount of water can causeseriouspersonal injury Useextra caution when workingwith hot water meters ...

Страница 16: ... of theproductsunder thiscontract will beadded to thepurchaseprice Buyer agreesto reimburseONICON for such tax or chargeor provideONICON with an acceptableexemption certificate Payment of invoiceswill bedue30 daysfrom thedateof shipment of theproductscontained therein In theevent that payment of an invoiceisnot received by theinvoiceduedate ONICON will assessalatefeenot to exceed 1 5 per month or ...

Отзывы: