29733 R2  06/01/2003

 

17

motor wiring, or replace the fan belt. Finally, restore 
power to the furnace. 
 
E)  Operate the furnace through a minimum of three full 
heating cycles. During this time, check for fuel oil leaks, 
gross air leakage from the supply air ductwork, unusual 
noises originating anywhere within the heating system 
which may cause some concern or annoyance to the 
home owner, etc.  
 
F)  Be sure that the homeowner is familiar with the 
furnace. The homeowner should be aware of the location 
of electrical circuit breaker or fuse, the location of any 
electrical switches controlling the furnace, the location of 
the oil tank shut-off valve and how to operate the valve. 
The homeowner should know where the oil tank gauge is 
located and how to read it. 
 
It would be beneficial to review safety issues with the 
home owner, such as the danger of storing combustibles 
too close to the furnace, hanging anything on the furnace 
vent pipe, and especially the dangers of indiscriminately 
pressing the burner reset button. 
 

IMPORTANT

: Be sure that the home owner knows where 

the burner reset switch is located, and is aware that the 
reset switch is not to be activated more than once without 
a look for the cause of the problem, (lack of fuel, etc.). Be 
sure that the homeowner knows when to quit trying to 
start the furnace during these conditions and who to call 
for emergency service. 
 

21.  OPERATING INSTRUCTIONS 

Before Lighting 

Open all supply and return air registers and grilles. 
Open all valves in oil pipes. 
Turn on electric power supply. 
 

To Light Unit 

Set the thermostat above room temperature to call for 
heat. The burner will start. NOTE: If the furnace has been 
off for an extended period of time, it may be necessary to 
press the RESET button on the primary combustion 
control relay, (once only). If pressing the reset button 
does not start the furnace, refer to Appendix C, 
Troubleshooting. 
 
After 30 or 45 seconds (depending on EFT), as the 
furnace becomes warm, circulation fan will start. 
 
The furnace will continue to run until the thermostat call 
for heat is satisfied. 
 
Set the thermostat below room temperature. The oil 
burner will stop. 
 

The air circulation blower will continue to run for 60, 90, 
120 or 150 seconds after the oil burner has stopped, 
depending on the dip switch settings. 
 

To Shut Down Unit 

Set the thermostat to the lowest possible setting. 
Set the manual switch (if installed) in the Electrical Power 
Supply Line to "OFF". 
 
NOTE: If the furnace is to be shut down for an extended 
period of time, close the oil supply valve to the oil burner.  
 
 

 

DO NOT ATTEMPT TO START THE BURNER WHEN 
EXCESS OIL HAS ACCUMULATED, WHEN THE 
FURNACE IS FULL OF VAPOUR, OR WHEN THE 
COMBUSTION CHAMBER IS VERY HOT. NEVER 
BURN GARBAGE OR PAPER IN THE FURNACE, AND 
NEVER LEAVE PAPER OR RAGS AROUND THE UNIT. 

 
 

Содержание Air Furnace

Страница 1: ...REGULATION OF AUTHORITIES HAVING JURISDICTION AND NFPA STANDARD 31 U S A OR CSA STANDARD B139 CAN FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors or liquids in the vicinity of t...

Страница 2: ...e Beckett Oil Burner 4 tons of cooling Highboy 2 nd Generation Heat Exchanger Nominal Output BTUH 80 Compact Highboy 120 Standard Highboy Breech Location F Front Cooling Airflow 3 3 Tons 4 4 Tons 5 5...

Страница 3: ...n Set Up 16 21 Operating Instructions 17 Table A 1 Beckett AF Oil Burner Set Up 18 Table A 2 Riello 40F Oil Burner Set Up 18 Table A 3 Direct Drive Blower Set Up 19 Table A 4 Direct Drive Blower Chara...

Страница 4: ...ecedence over the general instructions provided with this installation manual When in doubt please consult your local authorities All models are shipped assembled and pre wired The furnace should be c...

Страница 5: ...arging right by following these steps 1 Rotate the furnace 90 to the desired position 2 Remove the three nut and washer sets fastening the oil burner assembly to the furnace Beckett Burner or loosen t...

Страница 6: ...t be a means of control to prevent the operation of either system unless the dampers are in the full heat or full cool position The air heated by the furnace shall not pass through a refrigeration uni...

Страница 7: ...surrounding objects Observation Extend chimney above all surrounding objects within 30 feet B Chimney Cap or ventilator Observation Remove C Coping restricts opening Observation Make opening as large...

Страница 8: ...e chimney at a rate of one quarter inch to the foot The flue pipe should not be smaller in cross sectional area than the flue collar on the furnace The flue pipe should connect to the chimney such tha...

Страница 9: ...rotected against over heating by fixed high temperature limits These controls are factory set and are not field adjustable If an over temperature condition is detected one or both limit switches will...

Страница 10: ...on should be carried out in accordance with the humidifier manufacturer s installation instructions Water or water droplets from the humidifier should not be allowed to come into contact with the furn...

Страница 11: ...0 230 9 5 25 100 11 20 65 For additional information see the installation information sheet included in the documents envelope or affixed to the oil burner NOTE Both the Beckett and Riello oil burners...

Страница 12: ...ctrode porcelains should be free of cracks the electrode tips should be tapered and free of burrs and the contact rods must be clean and be in firm contact with the ignition transformer contact spring...

Страница 13: ...a sign of unburned fuel This indicates poor combustion This type of problem may be caused by excess draft excess air or contaminated fuel Do not ignore this indicator STACK TEMPERATURE Stack temperatu...

Страница 14: ...odating both wires on a single motor tap It is also acceptable to connect the selected motor speed with a pigtail joined to both heating and cooling speed wires with a wire nut As a safety precaution...

Страница 15: ...ntly high voltages to damage accessory equipment Use the terminals provided on the ST9103 EFT DO NOT START THE BURNER OR BLOWER FAN UNLESS THE BLOWER ACCESS DOOR IS SECURELY IN PLACE Additional ST9103...

Страница 16: ...ly air and return air temperatures when the furnace has reached steady state conditions This is the point at which the supply air temperature stops increasing relative to the return air temperature Th...

Страница 17: ...to start the furnace during these conditions and who to call for emergency service 21 OPERATING INSTRUCTIONS Before Lighting Open all supply and return air registers and grilles Open all valves in oi...

Страница 18: ...United States the R W Beckett AFG Burner may be equipped with Beckett s Inlet Air Shut Off Beckett Part No AF A 5861 to increase efficiency It reduces the amount of air passing through the oil burner...

Страница 19: ...on temperature rise Upper values may exceed measured airflow values in Table A 3 2 Nominal Values Only TABLE A 4 DIRECT DRIVE BLOWER CHARACTERISTICS CFM External Static Pressure inches w c Furnace Mo...

Страница 20: ...TERISTICS CFM External Static Pressure inches w c Furnace Model Motor hp Blower Temp Rise DT Motor FLA Motor Pulley Turns Out 0 20 0 30 0 40 0 50 0 60 0 70 0 1596 1518 1435 1330 1247 1184 1 1505 1434...

Страница 21: ...ons inches Plenum Openings Cabinet Supply Air Return Air Flue Width A Depth B Height C D x E Side F x G Bottom Dia Height H Filter Perm Ship Weight lb 80F 22 31 49 20 x 20 14 x 22 14 x 22 5 42 16 x 25...

Страница 22: ...29733 R2 06 01 2003 22 WIRING DIAGRAM OIL FURNACE WITH ST9103 EFT R7184 CONTROL Appendix B WIRING...

Страница 23: ...29733 R2 06 01 2003 23 WIRING DIAGRAM OIL FURNACE WITH ST9103 EFT RIELLO OIL BURNER Appendix B WIRING...

Страница 24: ...well as 115 volts to a line voltage humidifier or humidifier step down transformer Both sets of terminals are inch quick connect type rated at 1 A each The EAC terminals provide power to an electronic...

Страница 25: ...rk for 10 sec a Provides continuous spark after flame is sensed to assure that burner remains lit b Turns on LED diagnostic light c Starts carryover timer i Flame and call for heat are monitored If fl...

Страница 26: ...TAT SATISFIED R7184 SHUTS OFF Burner Motor Solenoid Valve LED Diagnostic Light RETURNS TO IDLE STATE FLAME FLAME FLAME FLAME NO FLAME NO FLAME FLAME LOST FLAME LOST REMAINS IN IDLE STATE R7184 SEQUENC...

Страница 27: ...good contact between control box spades and sub base terminals Defective control box Replace Verify electrical connections Check for seized pump motor or fan against housing Defective motor capacitor...

Страница 28: ...alve closed dirty filter damaged supply lines Defective or dirty oil valve stem nozzle or pump strainer Broken pump drive key defective pump no oil pressure Ignition electrodes shorted cracked porcela...

Страница 29: ...seconds b Burner motor is de energized even though thermostat is still calling for heat c If circulator fan has started it continues through the selected heat fan off delay period Established flame f...

Страница 30: ...call for heat a Circulator fan turns off when heat fan off delay time is complete b Normal operation resumes ST9103 control is in standby mode awaiting next thermostat command FAN Continuous circulati...

Страница 31: ...flame or viewing ambient light The resistance of the cad cell may be checked while the R7184 is in the run state by pressing the reset button The LED diagnostic light will flash the following code TA...

Страница 32: ...n there is a call for heat Procedure Status Corrective Action 1 Check that limit switches are closed and contacts are clean This includes the burner motor reset button N A N A 2 Check for line voltage...

Страница 33: ...ndicator light flashing at 1 Hz rate second on second off Procedure Status Corrective Action 1 Check that the limit switches are closed and contacts are clean 2 Check for line voltage power at the oil...

Страница 34: ...by pushing in and releasing red reset button Indicator light continues to flash at 1 Hz rate Verify that the control is not in restricted mode See notes at end of this table If not in restricted mode...

Страница 35: ...n socket Reconnect line voltage power and close line switch Start burner Burner keeps running System is OK Indicator light is on Remount control onto burner housing Go to step 6 10 Check cad cell Disc...

Страница 36: ...ND GENERAL TROUBLESHOOTING Problem Possible Cause Remedy Thermostat not calling for heat Check thermostat and adjust Also check thermostat for accuracy if it is a mercury switch type it might be off l...

Страница 37: ...l is getting dirty If cad cell is poorly aimed realign it NOTE The photocell should have a resistance of 100K W in absence of light a maximum of 1500 W in the presence of light Ensure that room light...

Страница 38: ...ose as possible to this fan off temperature Fuel oil leak Check fuel oil line for leaks Repair or replace if necessary Stack temperature too high Check stack temperature Stack temperatures will normal...

Страница 39: ...an motor amperage draw Check motor ventilation ports clean if necessary Replace motor if necessary Furnace will not warm home to desired temperature Burner motor stopping intermittently on overload Ch...

Страница 40: ...or Contact Address Postal Code Telephone No After Hours No Service Contractor if different from Installation Contractor Service Tech Telephone No After Hours No Fuel Supplier Oil Supplier Contact Tele...

Отзывы: