OneFex CS-IO1600DI Скачать руководство пользователя страница 13

13

13 

 

CS-IO1600DI User Manual 

             

 

Spare 

03ECH 

Spare 

 
Baud rate value corresponding table 

 

 

 

 

4.3  Command List 

 

Scene 

RTU format (send in hexadecimal) 

Query 4 DI

s ‘status 

FE 02 00 00 00 08 6D C3 

Return query information 

FE 02 01 07 D0 5E 

Query 16 DI

s ‘status 

01 02 00 00 00 10 79 C6 [Unicast Send]  
FE 02 00 00 00 10 6D C9 [Broadcast] Send] 

Return query information 

01 02 02 00 00 B9 B8[Unicast Send] 
FE 02 02 00 00 AD AC[Broadcast] Send] 

 
4.4  Command Details 

 

4.4.1  Optocoupler Input 

Query optocoupler (2-way optocoupler) 
Sending code: FE 02 00 00 00 02 ED C4 

Field 

Meaning 

Note 

FE 

Device address 

 

02 

02 command 

Query discrete input (optocoupler input) status 
command 

00 00 

Address 

Register address of the first optocoupler to be 
queried 

00 02 

Command 

Number of optocoupler states to query 

6D C6 

CRC16 

CRC16 checksum of the first 6 bytes of data 

 
 

Value 

Baud rate 

9600 

2400 

4800 

9600 

19200 

38400 

 

Содержание CS-IO1600DI

Страница 1: ...1 13 CS IO1600DI User Manual CS IO1600DI Serial I O Module Manual...

Страница 2: ...ng 10 3 2 3 Software Address Setting and Reading 10 3 2 4 Baud Rate Reading and Setting 11 4 DEVELOPMENT DATA INSTRUCTION 11 4 1 Communication Protocol Instruction 11 4 2 Modbus Register Instruction 1...

Страница 3: ...CS IO1600DI User Manual 5 2 5 PLC and the device cannot communicate normally 17 5 2 6 How to restore the factory settings 17 6 AFTER SALE SERVICE 17 6 1 Commitment 17 6 2 Disclaimer 18 7 UPDATE HISTOR...

Страница 4: ...es and precautions in this manual Please open the package carefully and check whether the device and accessories have been damaged due to transportation when you receive the device Please contact us f...

Страница 5: ...s It is 9600 by default and can be modified by software Support standard Modbus RTU protocol read and write by register address 0 255 Bulit in address DIP switch Set address codes by software Support...

Страница 6: ...0 20mA RS485 1 Address Dial CS IO404A 4 0 4 0 20mA RS485 1 Address Dial CS IO404 4 4 0 RS485 1 Address Dial CS IO606 6 6 0 RS485 1 Address Dial CS IO808 8 8 0 RS485 RS232 CS IO1600DI 0 16 0 RS485 RS2...

Страница 7: ...when one device is mounted on the network 2 2 1 RS485 Wiring 2 2 2 RS232 Wiring 2 3 DI Wiring The switch input interface is compatible with wet and dry nodes please pay attention to the different con...

Страница 8: ...ctive Signal Wiring It is suitable for measuring signals with voltage such as level high and low and pulse output 2 3 2 Passive Switch dry contact Wiring It is suitable for collecting passive contact...

Страница 9: ...at appears after the USB to 485 232 device is inserted is the serial port number 3 2 Device Address 3 2 1 Introduction The Offset Address of this device is 1 by default and the broadcast address is 25...

Страница 10: ...ally click read address on the serial relay debugging software to read the current address of the device only support broadcast read address when there is one device on the bus 3 2 3 Software Address...

Страница 11: ...ll take effect immediately after the operation 4 Development Data Instruction 4 1 Communication Protocol Instruction This product supports standard Modbus commands For detailed command generation and...

Страница 12: ...ut 7 0006H The 7th DI Input 8 0007H The 8th DI Input 9 0008H The 9th DI Input 10 0009H The 10th DI Input 11 000AH The 11th DI Input 12 000BH The 12th DI Input 13 000CH The 13th DI Input 14 000DH The 1...

Страница 13: ...rmation 01 02 02 00 00 B9 B8 Unicast Send FE 02 02 00 00 AD AC Broadcast Send 4 4 Command Details 4 4 1 Optocoupler Input Query optocoupler 2 way optocoupler Sending code FE 02 00 00 00 02 ED C4 Field...

Страница 14: ...g Note FE Device address 02 02 command Query discrete input optocoupler input status command 00 00 Address Register address of the first optocoupler to be queried 00 10 Command Number of optocoupler s...

Страница 15: ...n condensation or liquid immersion environments 5 The relay is a component with a certain service life When the theoretical service life is reached please replace it in time to avoid danger 5 2 FAQ 5...

Страница 16: ...he relay cannot switch normally 5 2 3 485 interface cannot be used to establish communication and control After the relay powered on 1 Check whether the 485 line is reversed and whether the voltage is...

Страница 17: ...ctory settings You can use the DIP switch to restore the factory settings Operation steps Power on dial all the dial codes to ON and toggle bit5 back and forth 6 times Dial all the dial codes then you...

Страница 18: ...ess or implied for the sale and or use of this product including the product s fitness for a particular purpose merchantability or liability for infringement of any patent copyright or other intellect...

Отзывы: