background image

 

INSTRUCTION/INSTALLATION SHEET  

HMS EZ-SCENE ALC LIGHTING INTERFACE

 

           

IS-0311 REV. A

 

 

 

 

 

 

3. Control Connections 

 

Terminals indicated as “A” in Figure 3, provide connections for 
communication to ALC controls.  Branch nos. 1 - 4 can have up 
to 31 ALC controls directly connected to them via up to 500 feet 
of category rated cable. 
 

Note: Part no. 364806-01 provides a single ALC 
communication branch.  Terminal connections for branches 2 - 
4 will not be present.   Part no. 364806-02 provides terminal 
connections for all four communication branches. 

 
Inputs 1 - 4, indicated as “B” in Figure 3, provide terminal 
connections for On-Q’s part no. 364697-01 RF Remote Control 
Receiver or other external device outputs. These four logic-level 
inputs simulate the four buttons of an ALC Scene Switch.  These 
inputs are referred to as Virtual Scene Switch Inputs. Each one 
of the four inputs can have an EZ-Scene program assigned to it.  
The external device may provide dry contact or voltage outputs 
(5-12VDC) to the inputs. The external device’s outputs must be 
configured  as  normally  open/logic  high  (5-12VDC).  A  virtual 
switch press is registered when the external device’s outputs 
become closed/logic low (<0.8VDC) for at least 100msec. All 
contact closures or voltages are applied between each input 
connection and GND. 
 

 
 
 
External devices requiring 12VDC power, such as ALC Branch 
Hub (P/N 364677-01 and P/N364736-01) or RF Remote 

Control Receiver (P/N364697-01), may draw their power from 
the HMS Controller’s AUX 12V and GND power connections.  
The 12VDC power connections are indicated as “C” in Figure 3.

Note: Do not exceed the HMS controller’s device load limit. 
Consult the HMS controller’s installation manual for device 
load ratings. 

 
ALC controls may be connected directly to the branch 
communication terminal connections as shown in Figure 4. 
Correct polarity must be maintained.  

 

Figure 3. Input and Branch Communication Connections

Figure 4. Direct ALC Communication Wiring

 

 

 

 

 

 

 

 

 

 

 

 

                             

Page 2 of 4

 

301 Fulling Mill Road, Suite G          ©Copyright 2005 by OnQ Technologies, Inc All Rights Reserved. 

Middletown, PA   17057 

            www.onqhome.com 

(800)-321-2343 