2015-01-07
Page 2/9
Inputs
•
Bus for KSUA master unit (RS485).
•
Terminals 1,2. Switchable between
External control unit and Night mode. For
example, opening the circuit has the same
effect as a triggered smoke detector (Both
groups affected).
•
Detector 1. Terminals 3,4
•
Detector 2. Terminals 5,6
•
Input for 230V 50Hz
Dimensions
SUM ALARM
ERROR
FIRE ALARM
OPERATION
NO
RM
A
L
RESET / TEST
(Press and hold 5sec
for damper test)
DAMPER
STATUS
230V 50Hz 20VA
Status Flash
NO
RM
A
L
O
FF
O
FF
1
2
FAN ON
KSUG
ON Control AB
Gånghester, Sweden.
Tel. +46 33 25 65 70
DETECTOR
SERVICE DET.
TEST CYCLE
Control Panel
Detector failure
Detector needs cleaning
Damper error at test cycle
Definitions
•
Ventilation dampers
Dampers that are closed by a spring.
•
Evacuation dampers
Dampers that are opened by a spring.
•
Day mode
Ventilation dampers open and evacuation
dampers closed.
•
Night mode
All damper types are closed.
•
Forced opening
All dampers are open.
Description of the KSUG in a
network
(Jumper H must be OFF)
The KSUG will only work in a network if the
KSUA has been correctly installed. To
communicate, the KSUA and KSUG use a
communication protocol which, at level 1, is
based on RS485. The physical connections are
two-wire links which must also have a ground.
In other words, the units must be linked with
three wires. Experience shows that the system
often works with just two wires, An example
of a widely used cable type is FKAR-PG
2*0.5. This is a 2-wire cable with screen. The
screen is used as the ground and should ONLY