NM - non maintained M - maintained
Type
Model
Light source
Time
Function
Luminous flux
Accessories
Recessed mounting
Flag mounting
EMY
STANDARD VERSION
AUTOMATIC SEPARATE TEST
M/NM
193 lm / 128 lm
3 h
1 W / 7xLED
2981
EMY
M/NM
235 lm / 218 lm
1 h
2 W / 14xLED
2982
EMY
M/NM
235 lm / 218 lm
3 h
2 W / 14xLED
2983
EMY
M/NM
193 lm / 128 lm
3 h
1 W / 7xLED
2984
EMY
M/NM
235 lm / 218 lm
1 h
2 W / 14xLED
2985
EMY
M/NM
235 lm / 218 lm
3 h
2 W / 14xLED
2986
Led indication
green
red
charging mode
led off
led on
led off
led on
test
emergency operation
error
led off
led on
led off
led on
1s
1s
1s
1s
1s
1s
1s
1s
1s
1s
1s
led off
led on
led off
led on
led off
led on
charging
charged
led off
led on
1s
1 2 3 4 5
850°C
10-40
°C
KO-I.OM-OS.V1.0/28.10.2016
Attention!
1. Luminare installation should be conducted with power supply turned off and in accordance with safety rules,
building norms and norms referring to electric installations.
2. Power supply for fitting should not be connected from circuits which can be loaded with induce receivers
– this may damage electric module in the fitt ing.
3. The fitting is adjusted to indoor usage.
4. The manufacturer reserves the right to change the design of the product.
5. The manufacturer is not liable for any damage caused by connection of the product to defective electrical
installation.
6. The luminaire should be positioned so that prolonged staring into the luminaire at a distance closer
than 0.4 m is not expected.
7. Risk Group 2
CAUTION. Possibly hazardous optical radiation emitted from this product.
Do not stare at the operating light source. May be harmful to the eye.
OMS spol. s r.o.
,
906 02 Dojč, 419, Slovakia, tel: +421 34 694 0811, www.omslighting.com
The guarantee shall not cover the normal wear and tear of battery packs and light sources. General warranty terms can be found on OMS
website: www.omslighting.com
Installation instructions
EMY 2980
OMS spol. s r.o.
906 02 Dojč, 419, Slovakia
Tel: +421 34 694 0811
www.omslighting.com
A
T
The module automatically conveys two test types:
Formating test
is performed after 48 hours from the start the device,
Test A
functional is performed every 30
days. Functional test continues: for modules 3 h — 60 seconds, for modules 1h, 2 h — 30 seconds.
Test B
of duration (corresponding to the nominal operation
time) performed regularly every 90 days.
Attention! Test A
will be shifted foward by 5h if power failure take place in the last 4h before this test.
Test B
will be shifted foward by 48h if power failure take
place in the last 24h before this test.
Tests can be done manually by using the test button:
Test A
— press the button for no more than 4 seconds.
Test B
— pressing the min. 5 seconds (test can be done after 48 hours of first use of the device).
Information for the nominal operation time!
After the start, the red led light goes out at 2 times per second: 1 time for 1 hour module, 2 times for 2 hours,
3 times for 3 hours.
ST
Testing correct operation of the fitting
Emergency lighting fitting has to be periodically tested in accordance with applicable regulations (norm PN-EN 50172). Test reports are available for inspection.
Everyday
Checking if the diode in the fitting lights up.
Once a month
Turn off the power supply or push the button activating test mode. The light source should light up and the green led diode
should turn off.
Once a year
Turn off its power supply and measure the duration. Check if the duration is not less than the nominal time.
IP65
230VAC
Ending notes
1. For cleaning use dry soft cloth. Using aggressive detergents and solvents
is forbidden.
2. Batteries and light source are replaceable. The light source contained in this
luminare shall only be replaced by the manufacturer or his service agent or
similar qualified person.
3. It is recommended to replace the battery every 4 years or when test errors
occurs.
4. LED module (light source) as an integral part of the fitting
5. To maintain the degree of protection IP, power cord should be carry through
the stuffing box or rubber conduit.
6. Used batteries lamps are products that undergo
utilization and they should be turned over to
utilization centresy.
7. Every cracked protective shield of the fitting should
be repleaced.
WARNING! Faults caused by disregarding fitting’s manual
invalidate warranty.
Power supply
230 V AC ± 10% / 50 - 60 Hz
Storage conditions
Power supply - CB version
230 V AC ± 10% / 50 - 60 Hz
tempe10 °C ÷ +25 °C
Duration of battery charging
< 24h
dry environment, not exposed to humidity and
chemical factors, away from strong magnetic fields
Protection level IP
IP 65
Temperature range t
a
t +10 °C ÷ +40 °C
a
-15 °C ÷ +40 °C
a
-15 °C ÷ +55 °C
a
store (bulk containers) in piles not higher than 1,2 m
Working humidity range (non-condensing)
Battery life
exchange after 4 years
or duration time is not maintain
maximum storage duration: 6 months
store in original packages
10% ÷ 85%