1. Installation of all Safety Rope Switch systems must be in accordance with a risk assessment for the individual application. Installation must only be carried out by
competent personnel and in accordance with these instructions.
2. Rope support eyebolts must be fitted at 2.5m. min. to 3m. max. intervals along all rope lengths between switches. The rope must be supported no more than 500mm
from the switch eyebolt or Safety Spring (if used). It is important that this first 500mm is not used as part of the active protection coverage.
3. M5 mounting bolts must be used to fix the switches. Tightening torque for mounting bolts to ensure reliable fixing is 4Nm. Tightening torque for the lid screws,
conduit entry plugs and cable glands must be 1.5Nm to ensure IP seal. Only use correct sizing glands for conduit entry and cable outside diameter.
4. Tensioning of rope is achieved by use of tensioner / gripper assemblies. Upon installation, tension to mid-position as indicated by the red arrows in the viewing
window of each switch. Check operation for all switches and the control circuits by puling the rope at various locations along the active protection area and resetting
each switch by depressing the Blue Reset button. Ensure each time that the switches latch off and require manual resetting by depressing the Blue Reset button.
Increase the system tension further, if required, depending upon the checks along the active length of coverage. If fitted with a Mushroom type E-Stop button (Red) then
test and reset each switch to ensure function of control circuits. Typical operational conditions for successful operation of system is less than 75N. pulling force and less
than 150mm deflection of rope between eyebolt supports.
5. Every week: Check correct operation of system at locations along all coverage length. Check for nominal tension setting, re-tension rope if necessary. Every 6
months: Isolate power and remove cover. Check screw terminal tightness and check for signs of moisture ingress. Never attempt to repair any switch.
Approvals
CE, ATEX per EC-Type Examination
Mechanical Features
Enclosure / Cover
Die-cast – painted yellow
External Parts
Stainless steel
IP Rating
IP67
Rope Spans Max
XER1022, XER1032 (heavy duty),
XER6022 (standard duty) = 80m
XER6022-SS = 100m
Mounting
4 x M5
Mounting position
Any
Conduit entries
3m cable (all models)
Torque settings
Mounting = M5 4.0 Nm
Lid = Torx M4 1.5 Nm
Terminals = 1.0 Nm
XER6022-SS = 316 stainless steel
Ambient Operating Temperature
-25C. to 80 C.
Vibration resistance
10-500Hz 0.35mm
Shock resistance
15g 11ms
Tension Force (typical mid setting)
130 N
Typical Operating Force (Rope pulled) < 125N. < 300mm deflection
Mechanical Life
1,000,000 operations
Weight
XER1022, XER1032 (heavy duty)
XER6022 (standard duty) 880 g
Electrical
Ex Classification
II 2 G
EEx d II C T6
Certificates
Baseefa11ATE0267X IECEx BAS 11.0133X
Contact Configuratoins
2NC, 1 NC + 1NO, 2NC + 2NO, 3NC + 1NO
Safety Contacts
1 N/C , 2NC
Rated Voltage AC15
400 VAC
250 VDC
250 VDC
Rated Curent CD13
2A AC
4A AC
0.15A DC
AC Ratings (switching)
250V
125V
Resistive
5A
5A
Inductive
3A
3A
DC Ratings (switching)
250V
125V
30V
Resistive
0.4A
0.8A
7A
Inductive
0.03A
0.06A
5A
Electric Life
1,000,000 operations
Information with regard to UL 508
Use polymeric conduit only. Use copper conductors only.
Electrical rating: A300. Type 1 enclosures
dual head 200m., single head 125m.
dual 1320 g. single 1100 g.
XER6022-SS 1635 g
XER Series
Operating Instructions for XER6022, XER6022-SS, XER1022 & XER1032
Exclusion of Liability Under the Following Circumstances
incorrect use
non-compliance with safety regulations
installation and electrical connection not performed by authorized
personnel.
failure to perform functional checks.
EC Declaration of Conformity
The manufacturer named below herewith declares that the product fulfills
the provisions of the directive(s) listed below and that the related standards
have been applied.
OMRON Scientific Technologies Inc.
6550 Dumbarton Circle
Fremont, CA 94555, U.S.A.
Directives applied:
Machinery directive 2006/42/EC
Low Voltage directive 2006/95/EC
Potential Explosive Atmosphere 94/9/EC
RoHS directive 2011/65/EC
Standards applied:
EN 60947-1:2007+A1:2011
EN 60947-5-1:2004:+A1:2009
EN 60947-5-5:1997+A1:2005
EN 60204-1:2006:+A1:2009
EN 60079-0:2011
EN 60079-1:2007
EN 60079-31:2009
ISO 13850:2006
ISO 13849-1
EN50013