4-1
Section
Controller
48
Tighten each screw to a torque of approximately 0.6 N
@
m.
Note
1. Make sure that the input voltage does not exceed a maximum permissible
input voltage of 26.4 V, otherwise the Controller may malfunction.
2. Separate power lines and high-tension lines from the input line in order to
protect the input line from noise interference.
Wiring SYNC Signal
Another Controller
Another Controller
Shielded wire
+
–
+
–
•
Connect the SYNC signals of other Controllers operating in synchronization.
•
If more than three Controllers operate in synchronization, two solderless termi-
nals must be connected to a single terminal. In that case, insert the solderless
terminals by overlapping the flat parts of the solderless terminals as shown be-
low. Then secure the solderless terminals with the screw.
Overlap the flat parts.
Note The SYNC+ and SYNC– lines each can have a total length of 300 m for the
whole system.