118
Procedures
Section 3-2
Monitoring Input Variables
and Output Variables in
Instances
The present values of input variables and output variables (parameters) are
displayed below the parameters.
Simulation of Ladder/ST
Programs in Instances
The CX-One Ver 1.1 (CX-Programmer Ver. 6.1) and later versions have a sim-
ulation function that can simulate the operation of a ladder program or ST pro-
gram within a function block instance. Both step execution and break point
operation are supported.
To return to the original instance, right-click in the ST program monitor window
and select
To Upper Layer
from the pop-up menu.
■
Enabling the Simulation Function
Use the following procedure to enable the simulation function.
1,2,3...
1.
Open the program containing the instance to be debugged.
2.
Select
View - Toolbars
and select the
Simulator Debug
Option in the
Tool-
bars
Tab.
3.
Select
Work Online Simulator
from the CX-Programmer’s
PLC
Menu and
transfer the program to the CX-Simulator in the computer.
Note
Steps 2 and 3 can be done in the opposite order.
■
Step Execution (Step Run)
Executes the program in step (instruction) increments. When the instance is
stopped, this function can move to the first step (instruction) of the ladder or
ST program in that instance.
The program in the instance can be executed with the Step Run or Continu-
ous Step Run method (see note).
Click the
OK
Button
to register.
Select
Register in Watch
Windows
.
or
Copy the instance and
paste it in the Watch
Window.
or
Right-click an empty row in
the Watch Window and
select
Register in Watch
Windows
.
PV of parameter for I/O variable.
Содержание SYSMAC CX-Programmer 9
Страница 2: ......
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 8: ......
Страница 16: ...xvi ...
Страница 20: ...xx ...
Страница 26: ...xxvi Application Precautions 4 ...
Страница 27: ...Part 1 Function Blocks ...
Страница 28: ......
Страница 154: ...128 Procedures Section 3 2 ...
Страница 155: ...Part 2 Structured Text ST ...
Страница 156: ......
Страница 160: ...134 CX Programmer Specifications Section 4 2 ...
Страница 206: ...180 Procedures Section 6 1 ...
Страница 208: ...182 System defined external variables supported in function blocks Appendix A ...
Страница 230: ...204 Revision History ...
Страница 231: ......