50
In the diagram below, a C20 CPU, a C40P CPU, a C20 I/O Unit and two I/O
Link Units can exchange data over a distance with a C500 Remote I/O Mas-
ter Unit. The C20 I/O Link Unit is set for IR 28 (which accesses IR 29 as
well), and the C40P I/O Link Unit is set for IR 30 (which accesses IR 31 as
well). The C40P I/O Link Unit is also set as the terminator.
C500 CPU Rack
C500 Remote I/O Master Unit
Optical fiber cable
Optical fiber cable
C20 CPU
I/O Link Unit
C40P CPU
C20P I/O Unit
I/O Link Unit
When setting the I/O Link Unit, in this example, it is necessary to take into
account not only the I/O words of the C500 Remote I/O Master Unit, but also
those of the C20 CPU and the C40P CPU.
C20P
C20P
C40P
OUT
IR 05
IN
IR 00
OUT
IR 06
IN
IR 03
C500 Word Assignment
0
1
2
27
28
29
30
31
Auto-
matic
Man-
ual
C20 Word Assignment
C40P Word Assignment
I/O Link
(C20)
I/O Link
(C40K)
OUT IR 05, IR 06
IN IR 00, IR 01
IN IR 02
OUT IR 07
OUT
IR 08
IN
IR 01
I/O Link Unit
DIP Switch Setting
Set for IR 28
Not terminator
Set for IR 30
Set as terminator
As seen from C20, C40P
IR 01: 16 input points
IR 06: 16 output points
Data input from C500
Data output to C500
IR 03: 16 input points
IR 08: 16 output points
Data input from C500
Data output to C500
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Model
I/O Link
(20)
I/O Link
(40P)
As seen from C20
IR 28: 16 output points
IR 29: 16 input points
Data output to C20
Data input from C20
IR 30: 16 output points
IR 31: input points
Data output to C40P
Data input from C40P
System Configuration
Example
Switch Settings
Section 2-8