253
View Trip Log [800]
Section 11-8
11-8 View Trip Log [800]
Main menu with parameters for viewing all the logged trip data. In total the
VSD saves the last 10 trips in the trip memory. The trip memory refreshes on
the FIFO principle (First In, First Out). Every trip in the memory is logged on
the time of the Run Time [731] counter. At every trip, the actual values of sev-
eral parameter are stored and available for troubleshooting.
11-8-1 Trip Message log [810]
Display the cause of the trip and what time that it occurred. When a trip occurs
the status menus are copied to the trip message log. There are nine trip mes-
sage logs [810]–[890]. When the tenth trip occurs the oldest trip will disap-
pear.
After reset of occurred trip, the trip message will be removed and menu [100]
will be indicated.
For fieldbus integer value of trip message, see message table for warnings,
[722].
Note
Bits 0–5 used for trip message value. Bits 6–15 for internal use.
Communication information
The information from the status menus are copied to the trip message log
when a trip occurs.
Unit:
h: m (hours: minutes)
Range:
0h: 0m–65355h: 59m
8x0 Trip message
Stp h:mm:ss
810 Ext Trip
Stp 132:12:14
Modbus Instance no/
DeviceNet no:
31101
Profibus slot/index
121/245
EtherCAT index (hex)
244d
Fieldbus format
UInt
Modbus format
UInt
Trip menu
Copied
from
Description
Process Value
Speed
Torque
Shaft Power
Electrical Power
Current
Output voltage
Frequency
DC Link voltage
Heatsink Temperature
PT100_1, 2, 3
VSD Status
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...