163
Process and Application Parameters [300]
Section 11-3
When the time set here is elapsed, the master drive will be changed. This
function is only active if Select Drive [393]=All and Change Cond [394]=
Timer/ Both.
Communication information
If a master drive is changed according to the timer function (Change Condi-
tion=Timer/Both [394]), it is possible to leave additional pumps running during
the change operation. With this function the change operation will be as
smooth as possible. The maximum number to be programmed in this menu
depends on the number of additional drives.
Example:
If the number of drives is set to 6, the maximum value will be 4. This function
is only active if Select Drive [393]=All.
Communication information
If the speed of the master drive comes into the upper band, an additional drive
will be added after a delay time that is set in start delay [399].
Default:
50 h
Range:
1-3000 h
Modbus Instance no/
DeviceNet no:
43165
Profibus slot/index
169/69
EtherCAT index (hex)
4c5d
Fieldbus format
UInt, 1=1 h
Modbus format
UInt, 1=1 h
Default:
0
Range:
0 to (the number of drives - 2)
Modbus Instance no/
DeviceNet no:
43166
Profibus slot/index
169/70
EtherCAT index (hex)
4c5e
Fieldbus format
UInt
Modbus format
UInt
Default:
10%
Range:
0-100% of total min speed to max speed
50h
A
A
0
10%
A
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...