128
Process and Application Parameters [300]
Section 11-3
This menu is not visible when speed, torque or frequency is selected. The
function sets the value of the maximum process value allowed.
Communication information
Ratio [326]
This menu is not visible when speed, frequency or torque is selected. The
function sets the ratio between the actual process value and the motor speed
so that it has an accurate process value when no feedback signal is used. See
Fig. 66.
Communication information
Fieldbus format
Long, 1=0.001
Modbus format
EInt
Default:
0
Range:
0.000-10000
Modbus Instance no/
DeviceNet no:
43311
Profibus slot/index
169/215
EtherCAT index (hex)
4cef
Fieldbus format
Long, 1=0.001
Modbus format
EInt
Default:
Linear
Linear
0
Process is linear related to speed/torque
Quadratic
1
Process is quadratic related to speed/torque
Modbus Instance no/
DeviceNet no:
43312
Profibus slot/index
169/216
EtherCAT index (hex)
4cf0
Fieldbus format
UInt
Modbus format
UInt
0
A
326 Ratio
Stp
Linear
A