4-4 Regenerative Energy Absorption
4
System Design
Wiring Method
Connect the External Regeneration Resistor between terminals P and B1.
Combining External Regeneration Resistors
Connect the thermal switch output so that the power supply is shut OFF
when the contacts open. Configure a sequence to shut OFF the power via
the thermal output. Not doing so may cause the resistor to overheat,
resulting in a fire or damage to the equipment.
Regeneration ab-
sorption capacity
*1
*1. Select a combination that has an absorption capacity greater than the average regeneration power (Pr).
20 W
40 W
70 W
140 W
Model
R88A-RR08050S
R88A-RR080100S
R88A-RR08050S
R88A-RR080100S
R88A-RR22047S
R88A-RR22047S
Resistance
*2
*2. Do not use a combination of resistors with a resistance lower than the minimum external regenerative
resistance of each Servo Drive. For information on the minimum external regenerative resistance, refer to
Servo Drive Regenerative Energy Absorption Capacity
50
Ω
/100
Ω
25
Ω
/50
Ω
47
Ω
94
Ω
Connection
method
P
B1
5
3
C
N
A
θ
>
Thermal S
w
itch O
u
tp
u
t
Ser
v
o Dri
v
e
External
Regeneration
Resistor
Precautions
for Correct Use
R
R
R
R
R