Switch Mode Power Supply
S8VS
■
Models with Total Run Time Monitor (S8VS-
@@@
24B
@
)
S8VS-06024B
The accumulated value of the operating time of the Power Supply is
displayed as the total run time.
0
(kh) will be displayed initially after
purchase and then the display will advance in 1-kh steps as the oper-
ating time accumulates. The S8VS-06024B, however, does not have
an alarm function (setting, display, or output).
S8VS-09024B
@
/S8VS-12024B
@
/
S8VS-18024B
@
/S8VS-24024B
@
The display will appear when the set value for the total run time has
been reached.
The accumulated value of the operating time of the Power Supply is
displayed as the total run time.
0
(kh) will be displayed initially after
purchase and then the display will advance in 1-kh steps as the oper-
ating time accumulates. When the total run time reaches the preset
alarm set value, the alarm (
a02
) and the total run time will be dis-
played alternately and a transistor ((12) total run time output terminal
(kh)) will output the status externally.
(Alarm set value reached = OFF, i.e., no continuity between (12) total
run time output terminal (kh) and (13) alarm output common termi-
nal)
The alarm set value can be changed in the setting mode.
Example: Alarm Displays When a Total Run Time Set
Value of 88 kh Is Reached
Note:
The total run time cannot be reset. To clear the alarm, change
the alarm set value to a value higher than the value displayed
for the total run time.
Time Chart
Note:
Setting is possible for the following models only:
S8VS-09024B
@
, S8VS-12024B
@
, S8VS-18024B
@
,
S8VS-24024B
@
Note: 1.
The total run time does not include the time that the Power
Supply is OFF.
2.
The total run time measures the total time that power is be-
ing supplied and is not related in any way to deterioration in
the electrolytic capacitor built into the Power Supply or to the
effects of the ambient temperature.
Operation mode
Total run time
Total run time
Total run time set value reached.
(See note.)
Output
voltage
Output
current
Peak hold
current
Note: The alarm (
a02
)
and the total run
time will be
displayed
alternately.
Total run time
50 kh
0 kh
AC input
Alarm output
Set value = 50 kh
(See note.)