Recommended Ferrules and Crimping Tools
Recommended Ferrules
Applicable to all the terminal blocks
Note: 1.
Make sure that the outer diameter of the wire is smaller than
the inner diameter of the insulating sleeve of the
recommended ferrule.
2.
Make sure that the ferrule processing dimensions conform
to the following figure.
Power input terminal block
Note: 1.
Make sure that the outer diameter of the wire is smaller than
the inner diameter of the insulating sleeve of the
recommended ferrule.
2.
Make sure that the ferrule processing dimensions conform
to the following figure.
Recommended Flat-blade Screwdriver
Use a flat-blade screwdriver to connect and remove wires. Use the
following flat-blade screwdriver.
The following table shows manufacturers and models as of 2018/Dec.
*
SZF 0-0,4X2,5 (manufactured by Phoenix Contact) is available to
order as OMRON's exclusive purchase model (XW4Z-00B).
Recommended Replacement Periods and Periodic Replacement for
Preventive Maintenance
The recommended replacement period for preventive maintenance is greatly influenced by the installation environment of the Power Supply. As
a guideline, the recommended replacement period is 7 to 10 years.
*
To prevent failures or accidents that can be caused by using a Power Supply beyond its service live, we recommend that you replace the Power
Supply as early as possible within the recommended replacement period. However, bear in mind that the recommended replacement period is for
reference only and does not guarantee the life of the Power Supply.
Many electronic components are used in the Power Supply and the Power Supply depends on the correct operation of these components to
achieve the original Power Supply functions and performance. However, the influence of the ambient temperature on aluminum electrolytic
capacitors is large, and the service life is reduced by half for each 10°C rise in temperature (Arrhenius law). When the capacity reduction life of the
electrolytic capacitor is reached, the Power Supply failures or accidents may occur. We therefore recommend that you replace the Power Supply
periodically to minimize product failures or accidents in advance.
*
The recommended replacement period applies under the following conditions: rated input voltage, load rate of 50% max., ambient temperature
of 40°C max., and the standard mounting method.
This product model is designed with a service life of 10 years minimum under the above conditions.
Applicable
wire
Ferrule
Conduct
or length
(mm)
Stripping
length
(mm)
(Ferrules
used)
Recommended Ferrules
(mm
2
) (AWG)
Phoenix
Contact
Weid
muller
Wago
0.25
24
8
12
AI 0,25-8
H0.25/12 FE-0.25-8N-YE
10
12
AI 0,25-10
---
---
0.34
22
8
12
AI 0,34-8
H0.34/12 FE-0.34-8N-TQ
10
12
AI 0,34-10
---
---
0.50
20
8
12
AI 0,5-8
H0.5/14
FE-0.5-8N-WH
10
12
AI 0,5-10
H0.5/16
FE-0.5-10N-WH
0.75
18
8
12
AI 0,75-8
H0.75/14 FE-0.75-8N-GY
10
12
AI 0,75-10
H0.75/16 FE-0.75-10N-GY
1/1.25 18/17
8
12
AI 1-8
H1.0/14
FE-1.0-8N-RD
10
12
AI 1-10
H1.0/16
FE-1.0-10N-RD
1.25/
1.5
17/16
8
12
AI 1,5-8
H1.5/14
FE-1.5-8N-BK
10
12
AI 1,5-10
H1.5/16
FE-1.5-10N-
BK
2.5
14
10
12
AI 2,5-10
H2.5/
16DS
FE-2.5-10N-
BU
Recommended crimp tool
CRIMPFOX6
CRIMPFOX6T-F
CRIMPFOX10S
PZ6 roto Variocrimp4
8 to 10 mm
2.6 mm max.
2.8 mm max.
Applicable
wire
Ferrule
Conduct
or length
(mm)
Stripping
length
(mm)
(Ferrules
used)
Recommended Ferrules
(mm
2
) (AWG)
Phoenix
Contact
Weid
muller
Wago
4
12
12
14
AI 4-12
H4.0/20D FE-4.0-12N-GY
6
10
12
16
AI 6-12
H6.0/20
FE-6.0-12N-YE
*
Recommended crimp tool
CRIMPFOX6
CRIMPFOX6T-F
CRIMPFOX10S
PZ6 roto
Variocrimp4
*
Use the
Variocrimp16.
Model
Manufacturer
ESD 0,40×2,5
Wera
SZS 0,4×2,5
SZF 0-0,4×2,5
*
Phoenix Contact
0.4×2.5×75 302
Wiha
AEF.2,5×75
Facom
210/-719
Wago
SDIS 0.4×2.5×75
Weidmuller
9900 (-2.5×75)
VESSEL
12 mm
4 mm max.
4 mm max.
0.4 mm
2.5 mm dia.
2.5 mm
Side