5-1 Checking the battery
5 Maintenance and inspection
S8BA-24D24D
□□□
LF
73
5
3.
Calculate the initial value of the backup time for the total capacity of the connected
devices from the graph below.
▪
Graph of backup time (graph of initial values for products that have not been used
at 25°C). The backup time becomes shorter than the graph (table) below when
temperature is lower.
0
10
20
30
40
50
60
70
80
90
100
110
120
0
60
120
180
240
300
360
420
480
120W
240W
360W
480W
Capacity (W)
Backup
time
(Minutes)
▪
The smaller the capacity of connected devices becomes, the longer the backup
time becomes.
Backup time table (Time unit: minutes)
Model
Capacity
(
Watt)
30
60
90
120
180
240
300
360
420
480
120W
29
14
9
6
240W
58
29
19
15
9
6
360W
87
43
28
22
14
10
8
6
480W
119
59
39
29
19
15
11
9
8
6
*These backup times are for reference only. Times may vary according to battery life and
external environmental conditions (temperature, etc).