Power Supply
Technical Information
9
Power
supp
lies
Power Supply Precautions for Correct Use
■
Installation
●
Mounting Methods
The standard mounting methods should
be used to ensure proper heat
dissipation. If other mounting methods
must be used, the ambient temperature
must be lowered or the load rate must
be reduced to prevent temperature
increase inside the Power Supply
caused by poor heat dissipation.
Refer to the information in the table on
the right.
DIN-rail Mounting Models: Main Models
Screw Mounting Models: Main Models
*1. The 300-W model can be used under given
conditions.
*2. The 600-W model can be used.
Yes: Can be used
No: Cannot be used.
Conditional: Can be used at an ambient tempera-
ture of 50
°
C (up to 50% of load rate).
Mounting direction
Standard
Horizontal
Face-up
Face-down
Model
S82K
OK
No
Conditional
No
S8TS
OK
No
No
No
S8VS(15, 30W)
OK
No
OK
No
S8VS (60, 90, 120,
180, 240 W)
OK
No
No
No
S8T-DCBU-01
OK
No
No
No
S8T-DCBU-02
OK
No
No
No
S8VM
OK
No
No
No
Mounting direction
Standard
Horizontal
Face-up
Face-down
Horizontal
Model
S82J
Yes
Yes *1
Conditional *2
Conditional *2
No
S8VM
Yes
Yes
Yes
No
No
●
Installation Space
When mounting two or more Power
Supplies side by side, be sure to provide
spacing between them as indicated in
the table on the right or greater.
Note. Be sure to provide an installation space that
allows for shielding (including ducts).
A
A
B
C
Fan
Fan
S82J
B
C
Front panel
Front panel
Spacing Required Between Power Supplies
(Unit: mm)
* Ambient temperature of 50
°
C: 100 mm
Model
Dimension A
Dimension B
Dimension C
S82J
20
20 (300, 600 W)
20 (300, 600 W)
S82K
10
---
---
S8VS
20
---
---
S8VM
20
---
---