6 Basic Parameter Settings
6 - 42
High-function General-purpose Inverter RX2 Series User’s Manual
An example of operation on [FUP] and [FDN] terminals is shown as follow:
Parameter
The input terminal 019 [AHD] analog command holding holds the command of the analog input when
the input terminal becomes ON. When the input terminal becomes OFF, the command returns to the
analog command.
If the main speed command [AA101] is an analog input command (01-03), this function is effective even
when data are held by the analog command holding [AHD] function.
If 019[AHD] function is effective, the held data can be moved up/down by using [FUP]/[FDN] function.
Precautions for Correct Use
Data changes with the [FUP]/[FDN] function are not saved.
Item
Parameters
Data
Description
Default
data
Main speed input
source selection,
1st-motor
[AA101]
01 to 15
01: Ai1-L input, 02: Ai2-L input, 03: Ai3-L input,
07: parameter setting,
08: RS485 communication,
12: pulse string input (main body),
14: program function, 15: PID arithmetic
01
*1
*1. Default data when default data selection (UB-02) is set to 01.
Input terminal function
selection
[CA-01] to
[CA-11]
020
FUP: Acceleration through remote operation
-
021
FDN: Deceleration through remote operation
022
UDC: Clearing of remote operation data
FUP/FDN overwriting
target selection
[CA-60]
00
Overwrites the frequency command.
00
01
PID target value is overwritten.
FUP/FDN data save
enable
[CA-61]
00
The command is not saved in case of power
shutdown.
00
01
The command is saved in case of power shut-
down.
FUP/FDN UDC
selection
[CA-62]
00
Cleared to 0 Hz.
00
01
Cleared to the saved command.
Acceleration time set-
ting for FUP/FDN func-
tion
[CA-64]
0.00 to
3600.00(s)
Sets acceleration time for FUP/FDN functions.
30.00
Deceleration time set-
ting for FUP/FDN func-
tion
[CA-66]
0.00 to
3600.00(s)
Sets deceleration time for FUP/FDN functions.
30.00
6-4-12 Analog Command Hold Function (AHD)
(FW,RV)
FUP
FDN
ON
ON
ON
ON
Operation command.
If [FUP] and [FDN] terminals are made ON simul-
taneously, acceleration/deceleration is not made.
Frequency command
Output frequency
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......