SIEPCYEUOQ2V01A Q2V Technical Manual
683
If you set
n5-03 [FF Control Gain]
too high, the motor speed will momentarily increase to more than the set
frequency.
◆
n6: ONLINE TUNING
n6 parameters
are used to set the online tuning function for motor line-to-line resistance.
The Online Tuning for motor line-to-line resistance is used to prevent degradation of speed control accuracy due
to motor temperature fluctuation and motor stalls due to insufficient torque.
■
n6-01: Online Tune Selection
No.
(Hex.)
Name
Description
Default
(Range)
n6-01
(0570)
Online Tune Selection
Sets the type of motor data that Online Tuning uses for OLV control.
0
(0 - 2)
0 : Disabled
1 : Line-to-Line Resistance Tuning
The drive adjusts the motor line-to-line resistance during run. This procedure is applicable for speed values 6 Hz
and less. It also adjusts the motor resistance value to increase the overload capacity in the low speed range.
2 : VoltageAdjustment
The drive adjusts the output voltage during run to increase overload tolerance and minimize the effects of high
temperatures on speed precision.
Note:
Setting 2 is enabled only when
b8-01 = 0 [eSave Ctrl Selection = Disabled]
.
■
n6-05: Online Tune Gain
No.
(Hex.)
Name
Description
Default
(Range)
n6-05
(05C7)
Expert
Online Tune Gain
Sets the compensation gain when
n6-01 = 2 [Online Tune Selection = VoltageAdjustment]
.
Usually it is not necessary to change this parameter.
1.0
(0.1 - 50.0)
When you use a motor that has a large secondary circuit time constant, decrease the setting value.
If the drive detects
oL1 [Motor Overload]
, increase the setting value in 0.1-unit increments.
◆
n7: SIMPLE VECTOR TUNING
The
n7 parameters
provide special adjustments for EZ Vector Control.
■
n7-01: LoFreq Damping Gain
No.
(Hex.)
Name
Description
Default
(Range)
n7-01
(3111)
Expert
LoFreq Damping Gain
Sets the oscillation suppression gain for the low speed range.
1.0
(0.1 - 10.0)
Note:
•
If oscillation occurs in the low speed range, increase the acceleration time or increase the setting value in 0.5-unit increments.
•
To get starting torque with the setting for
C4-01 [Trq Comp Gain]
, decrease the setting value in 0.3-unit increments.
■
n7-05: TrqCtrl Response Gain
No.
(Hex.)
Name
Description
Default
(Range)
n7-05
(3115)
Expert
TrqCtrl Response Gain
Sets the response gain related to changes in the load.
50
(10 - 1000)
Note:
To make tracking related to load changes better, increase the setting value in 5-unit increments. If oscillation occurs during load
changes, decrease the setting value in 5-unit increments.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...