7.10 Troubleshooting Without Fault Display
SIEPCYEUOQ2V01A Q2V Technical Manual
259
Causes
Possible Solutions
An incorrect password was entered in
A1-04 [Password Input]
.
•
Enter the correct password to
A1-04
again.
•
If you forgot the password, set the password again with
A1-04
and
A1-05 [Password Setting]
.
Note:
If the password is set, it will not be possible to change these parameters until the password
matches:
•
A1-01 [Access Level]
•
A1-02 [Control Method]
•
A1-03 [Init Parameters]
•
A1-06 [Macro Preset]
•
A1-07 [Q2pack Enable]
•
A2-01 to A2-32 [MAN1 Param1 to MAN3 Param12]
The drive detected
Uv [Undervoltage]
.
•
View
U1-07 [DC Bus Voltage]
to see the power supply voltage.
•
Examine the main circuit wiring.
◆
The Motor Does Not Rotate After Entering Run Command
Causes
Possible Solutions
The drive is not in Drive Mode.
1.
Make sure that the READY LED on the keypad is on.
2.
If the READY LED is off, push and hold the ESC Key to go back to the frequency reference
screen (the initial screen).
The drive stopped and you pushed
to transfer the Run command
source to the keypad.
Do one of these two:
•
Push
.
•
Re-energize the drive.
Note:
Set
o2-01 = 0 [LO/RE Key Selection of Function = Disabled]
to prevent changing the Run
command source with
.
Auto-Tuning completed.
Push and hold the ESC Key to go back to the frequency reference screen (the initial screen).
Note:
When Auto-Tuning completes, the drive changes to Programming Mode. The drive will not
accept a Run command unless the drive is in Drive Mode.
The drive received a Fast Stop command.
Turn off the fast stop input signal.
The settings for the source that supplies the Run command are incorrect.
Set
b1-02 [Run Comm. Sel 1]
correctly.
The frequency reference source is set incorrectly.
Set
b1-01 [Freq. Ref. Sel. 1]
correctly.
There is defective wiring in the control circuit terminals.
•
Correctly wire the drive control circuit terminals.
•
View
U1-10 [In Terminal Status]
for input terminal status.
The settings for voltage input and current input of the master frequency
reference are incorrect.
Examine these analog input terminal signal level settings:
•
Terminal AI1:
H3-01 [AI1 Signal Level Select]
•
Terminal AI2: DIP switch S1 and
H3-09 [AI2 Signal Level Select]
The selection for the sinking/sourcing mode and the internal/external power
supply is incorrect.
•
For sinking mode, close the circuit between terminals DIC-D24V with a wire jumper.
•
For sourcing mode, close the circuit between terminals DIC-D0V with a wire jumper.
•
For external power supply, remove the wire jumper.
The frequency reference is too low.
•
View
U1-01 [Frequency Reference]
.
•
Increase the frequency reference to a value higher than
E1-09 [Min Output Frequency]
.
The MFAI setting is incorrect.
•
Make sure that the functions set to the MFAI are correct. The frequency reference is 0 when
H3-02, H3-10 = 5 [MFAI Function Select = Freq Gain]
and voltage (current) is not input.
•
Use
U1-13, U1-14 [Terminal AI1 InputLv, Terminal AI2 InputLv]
to make sure that the analog
input values set to terminals AI1 and AI2 are applicable.
You pushed
.
Turn the Run command OFF then ON from an external input.
Note:
When you push
during operation, the drive will ramp to stop. Set
o2-02 = 0 [STOP
Key Selection of Function = Disabled]
to disable the
function.
The 2-wire sequence and 3-wire sequence are set incorrectly.
•
Set one of the parameters
H1-03 to H1-07 [DI3 Function Selection to DI7 Function Selection]
to
5 [3-Wire Seq.]
to enable the 3-wire sequence.
•
If a 2-wire sequence is necessary, make sure that
H1-03 to H1-07 ≠ 5
.
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...