SIEPCYEUOQ2V01A Q2V Technical Manual
247
7.6
Parameter Setting Errors
Parameter setting errors occur when multiple parameter settings do not agree, or when parameter setting values
are not correct.
Examine the parameter setting that caused the error, and remove the cause of the error. You must first correct the
parameter setting errors before you can operate the drive. The drive will not send notification signals for the faults
and alarms when these parameter setting errors occur.
Code
Name
Causes
Possible Solutions
oPE01
Drive Capacity Setting Error
The value set in
o2-04 [Drive KVA Selection]
does
not agree with the drive model.
Set
o2-04
to the correct value.
Code
Name
Causes
Possible Solutions
oPE02
Parameter Range Setting Error
Parameters settings are not in the applicable setting
range.
1.
Push
to show
U1-18 [oPE Fault Parameter]
, and find
parameters that are not in the applicable setting range.
2.
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other
oPExx
errors have priority over
oPE02
.
Set
E2-01 ≤ E2-03 [Mot Rated Current (FLA) ≤
Mot No-Load Current]
.
Make sure that
E2-01 > E2-03
.
Note:
If it is necessary to set
E2-01 < E2-03
, first lower the value
set in
E2-03
, and then set
E2-01
.
Code
Name
Causes
Possible Solutions
oPE03
Multi-Function Input Setting Err
The settings for these parameters do not agree:
•
H1-01 to H1-07 [Terminals DI1 to DI7 Function
Selection]
•
H7-01 to H7-04 [Virtual Multi-Function Inputs 1
to 4]
Correct the parameter settings.
The settings for MFDIs overlap.
Note:
This does not include
H1-xx = 20 to 2F [MFDI
Function Select = External Fault]
and
[Reserved]
.
Set the parameters correctly to prevent MFDI function overlap.
These pairs of MFDI functions are not set to Digital
Inputs (
H1-xx
and
H7-01 to H7-04
) at the same
time:
•
Setting values
62 [Up Command]
and
63 [Down
Command]
•
Setting values
65 [Up2 Command]
and
66 [Dw2
Command]
•
Setting values
3 [Run Command]
and
4 [FWD/
REV Cmd]
Set the MFDI pairs.
A minimum of two of these MFDI combinations are
set to Digital Inputs (
H1-xx
and
H7-01 to H7-04
) at
the same time:
•
Setting values
62 [Up Command]
and
63 [Down
Command]
•
Setting values
65 [Up2 Command]
and
66 [Dw2
Command]
•
Setting value
17 [Ac/Dec Hold]
•
Setting value
16 [Ref Sample]
•
Setting values
E to 10 [Add Offset Frequency 1
to 3 (d7-01 to d7-03)]
Remove the function settings that are not in use.
These commands are set in Digital Inputs (
H1-xx
and
H7-01 to H7-04
) at the same time:
•
Setting values
67 [SpdSrch Fmax]
and
68
[SpdSrch Fref]
•
Setting values
40, 41, 42, 43 [KEB Thru1 NC,
KEB Thru1 NO, KEB Thru2 NC, KEB Thru2
NO]
and
32 [HiSlipBraking]
•
Setting values
61 [Motor 2 Select]
and
19 [Ac/
Dec Time2]
•
Setting values
40, 41 [KEB Thru1 NC, KEB
Thru1 NO]
and
42, 43 [KEB Thru2 NC, KEB
Thru2 NO]
•
Setting values
1, 2 [Forward Run, Reverse Run]
and
3, 4 [Run Command, FWD/REV Cmd]
•
Setting values
30 [DCInj Cmd]
and
1A [Drive
Enable]
•
Setting values
61 [Motor 2 Select]
and
65, 66
[Up2 Command, Dw2 Command]
Remove the function settings that are not in use.
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...