Connect UPS Using the I/O Connector
The I/O connector of the Box PC Without Operating System:
• receives the power status of the UPS with the UPS Mode Input when the Box PC has a Windows
operating system. For other operating systems this input is not functional.
• indicates the power status of the Box PC to the UPS with the Power Status Output.
Additional Information
• A UPS connection using the I/O connector is only possible for a Box PC with a Windows op-
erating system. For all other operating systems use the USB connector to connect the UPS.
Refer to
5-8-1 Connect UPS Using the USB Connector
• The Box PC does not react automatically to the UPS Mode Input. A custom software program
is required to shut down the Box PC when needed.
UPS Drivers and the required software can be downloaded from the OMRON download site:
• Drivers for the S8BA UPS
• Installation files for the UPS Setting Utility (Windows only)
Precautions for Safe Use
• Always use the recommended uninterruptible power supply (UPS) to prevent data loss and
other system file integrity issues caused by unexpected power interruption.
• Use an Omron S8BA UPS with the correct revision number to prevent improper system shut-
down.
• Correctly perform wiring and setting, and ensure that the shutdown by the UPS can be exe-
cuted.
Follow the steps below to connect the S8BA UPS to the I/O connector of the Box PC and to configure
it correctly.
1
Ensure the revision number of the UPS is correct.
Refer to
on page 2 - 24 for more information.
2
Download the above mentioned software.
3
Wire the S8BA UPS.
(1) Wire the input of the UPS to the output of the Power Supply.
(2) Wire the output of the UPS to the power connector of the Box PC.
(3) Ground the UPS.
(4) Connect the Contact port of the S8BA UPS to the I/O port of the Box PC with the connec-
tion cable S8BW-02.
5 Installation
5 - 52
NY-series Industrial Box PC Without Operating System User's Manual (W586)
Содержание NYB17-*100 SERIES
Страница 8: ...CONTENTS 6 NY series Industrial Box PC Without Operating System User s Manual W586...
Страница 30: ...Revision History 28 NY series Industrial Box PC Without Operating System User s Manual W586...
Страница 32: ...Sections in this Manual 30 NY series Industrial Box PC Without Operating System User s Manual W586...
Страница 40: ...1 Overview 1 8 NY series Industrial Box PC Without Operating System User s Manual W586...
Страница 68: ...3 Software 3 4 NY series Industrial Box PC Without Operating System User s Manual W586...
Страница 189: ...I Index I 1 NY series Industrial Box PC Without Operating System User s Manual W586 I...
Страница 192: ......
Страница 193: ......