Item
Specification
OFF leak-
age cur-
rent
---
0.3 mA max.
Internal
I/O com-
mon
---
PNP
ON re-
sponse
time
---
0.5 ms max.
OFF re-
sponse
time
---
1.5 ms max.
Residual
voltage
---
1.2 V max. (0.5 ADC, between each output
terminal and G)
Short-cir-
cuit pro-
tection
---
Short-cir-
cuit de-
tection
---
Line dis-
connec-
tion de-
tection
---
*1.
Detects a short-circuit that occurred between the power (V) and power supply -(G) of the I/O con-
nectors to protect the IO-Link I/O Hubs.
*2.
Detects a disconnection of the power (V) of the I/O connectors.
*3.
Detects a short-circuit that occurred between pin 4 and the power supply -(G) and between pin 2 and the
power supply -(G) to protect the IO-Link I/O Hubs.
*4.
Detects a disconnection of pin 4 and pin 2 of the I/O connectors.
2 Specifications and Application Procedures
2-6
NXR-series IO-Link I/O Hub User’s Manual (W620)