4 - 7
4 Installation and Wiring
NX-series CPU Unit Hardware User’s Manual (W535)
4-
2 Fai
l-saf
e Circuit
s
4
4-
2-1 Ord
er of Powe
rin
g Up the C
ontrolle
r and C
ontrolle
d System
Outputs from Units, such as DC Output Units, may malfunction momentarily when the power to the
Controller is turned ON. This may cause problems in the system if the Controller power supply is turned
ON after the controlled system’s power supply. To prevent possible malfunctions, add an external circuit
that prevents the power supply to the controlled system from going ON before the power supply to the
Controller itself.
Precautions for Safe Use
It takes approximately 10 to 20 seconds to enter RUN mode after the power supply is turned
ON. During that time, outputs will be OFF or the values will be according to settings in the Units
or slaves. Also, external communications cannot be performed.
Use the RUN output on the Power Supply Unit, for example, to implement fail-safe circuits so
that external devices do not operate incorrectly.
It is possible for an output to remain ON due to a malfunction in the internal circuitry of the Output Unit,
such as a relay or transistor malfunction. Be sure to add any circuits necessary outside of the Controller
to ensure the safety of the system in the event that an output fails to go OFF.
The following emergency stop circuit controls the power supply to the controlled system so that power
is supplied to the controlled system only when the Controller is operating and the RUN output is ON. An
external relay (CR1) is connected to the RUN output from the Power Supply Unit as shown in the fol-
lowing diagram.
4-2-1
Order of Powering Up the Controller and Controlled System
Output Unit Failure
Power Supply Wiring and Emergency Stop Circuit
MCB1
MCB2
CR1
Transformer
or noise filter
Twisted-pair wires
Power supply
Controlled system
Controller
DC voltage
regulator
Surge suppressor
DC
input/output
+
-
Controller RUN
output
CR1
Содержание NX701-1620
Страница 11: ...9 Manual Structure NX series CPU Unit Hardware User s Manual W535...
Страница 46: ...Sections in this Manual 44 NX series CPU Unit Hardware User s Manual W535...
Страница 64: ...1 Introduction to NX series Controllers 1 18 NX series CPU Unit Hardware User s Manual W535...
Страница 72: ...2 System Configuration 2 8 NX series CPU Unit Hardware User s Manual W535...
Страница 90: ...3 Configuration Units 3 18 NX series CPU Unit Hardware User s Manual W535...
Страница 156: ...6 Inspection and Maintenance 6 14 NX series CPU Unit Hardware User s Manual W535...
Страница 163: ...I 1 I NX series CPU Unit Hardware User s Manual W535 Index...
Страница 166: ...I 4 NX series CPU Unit Hardware User s Manual W535 Index...
Страница 167: ......