Sends data to a node on the network.
Instruction
Name
FB/
FUN
Graphic expression
ST expression
Send
Send to Net-
work
FB
Send
Send
_instance
Execute
DstNetAdr
Done
CommPort
SrcDat
SendSize
DstCh
Option
Error
ErrorID
DstArea
Busy
ErrorIDEx
Send_instance(Execute, DstNe-
tAdr, CommPort, SrcDat, Send-
Size, DstArea, DstCh, Option,
Done, Busy, Error, ErrorID, ErrorI-
DEx);
Variable
Name
Input/
output
Contents
Valid range
Unit
Initial
value
DstNetAdr
Network address at
send destination
Input
Specifies the network
address and node ad-
dress at send destina-
tion
---
---
---
CommPort
Designation of port at
send destination
Specifies the serial
port at send destina-
tion
_NONE
---
_NONE
SrcDat[] ar-
ray
First element of array
at send destination
Beginning of data (ar-
ray) to be sent
16#0000 to
16#FFFF
---
SendSize
Number of send words
Specifies the number
of words in the send
data
0 to Max. data
Word
1
DstArea
Area at send destina-
tion
Specifies the area type
at send destination
_CIO
_WR
_HR
_TIMER
_COUNTER
_DM
_EM0
⋮
_EM18
---
_DM
DstCh
CH at send destination
Specifies the first ch at
send destination
0 to 32,767
ch
0
Option
Response
Specifies response
monitoring and resend-
ing
---
---
---
*1.
If you omit an input parameter, the default value is not applied. A building error will occur.
*2.
This may vary depending on the network type.
3 Client Function
3 - 4
NX-series CPU Unit FINS Function User's Manual (W596)
Содержание NX102-10 Series
Страница 24: ...Sections in this Manual 22 NX series CPU Unit FINS Function User s Manual W596...
Страница 36: ...2 Server Function 2 6 NX series CPU Unit FINS Function User s Manual W596...
Страница 40: ...2 Server Function 2 10 NX series CPU Unit FINS Function User s Manual W596...
Страница 65: ...I Index I 1 NX series CPU Unit FINS Function User s Manual W596 I...
Страница 67: ......