Item
Specification
Installation orientation and re-
strictions
Installation orientation:
•
Connected to a CPU Unit or a Communication Control Unit
Possible in the upright installation orientation.
•
Connected to a Communications Coupler Unit
Six possible orientations.
Restriction: Maximum ambient temperature is 50°C for any orientation oth-
er than upright installation.
Protective functions
Overvoltage protection circuit and short detection (test outputs)
*1.
Only NX102 CPU Units and Communication Control Units can be connected. NX1P2 CPU Units cannot be
connected.
2-2-2
Part Names and Functions
This section provides the names and functions of the parts of the Safety Input Unit.
(C)
(D)
(H)
(G)
(F)
(C)
(A)
(E)
(C)
(E)
(C)
(B)
(B)
Letter
Name
Function
(A)
Marker attachment loca-
tion
The locations where markers are attached. The markers made by OMRON
are installed for the factory setting. Commercially available markers can also
be installed.
Refer to
(B)
NX bus connector
This is the NX-series bus connector.
(C)
Unit hookup guides
These guides are used to connect two Units.
(D)
DIN Track mounting
hooks
These hooks are used to mount the NX Unit to a DIN Track.
(E)
Protrusions for removing
the Unit
The protrusions to hold when removing the Unit.
(F)
Indicators
The indicators show the current operating status of the Safety Input Unit or
signal input status.
Refer to
(G)
Terminal block
The terminal block is used to connect external devices.
(H)
Unit specifications
The specifications of the Safety Input Unit are given here.
2 Specifications
2 - 22
NX-series Safety Control Unit User's Manual (Z930)
Содержание NX-SIH400
Страница 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Страница 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Страница 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Страница 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Страница 378: ...7 Checking Operation and Actual Operation 7 72 NX series Safety Control Unit User s Manual Z930 ...
Страница 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Страница 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Страница 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Страница 550: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 38 NX series Safety Control Unit User s Manual Z930 ...
Страница 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 558: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 46 NX series Safety Control Unit User s Manual Z930 ...
Страница 564: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 52 NX series Safety Control Unit User s Manual Z930 ...
Страница 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Страница 625: ......