5-4
Setting Up the Safety Process Data
Communications
5-4-1
Setting Up the FSoE Communications
When the Safety Control Unit is placed on the NX bus in the Sysmac Studio CPU rack configuration,
EtherCAT network configuration, and EtherCAT slave terminal configuration, the FSoE communica-
tions are set up automatically.
Use the following procedure to view or change the settings for the FSoE communications.
1
In the Multiview Explorer, select the target Safety CPU Unit in the Controller Selection Box.
2
Select
Configurations and Setup
–
Communications
–
Safety
, and then double-click
Safety
I/O
.
The meanings of the items in the Safety I/O Tab Page are given below.
Item
Editing
Description
Position
Not
possible
•
Node address
Fixed to NXBusMaster when connected to the CPU rack.
For a connection to an EtherCAT Coupler Unit, the node number of the Unit as an
EtherCAT slave is displayed.
"EIP" is displayed for a connection to an EtherNet/IP Coupler Unit.
•
Unit number
It displays the NX Unit number of the Safety I/O Unit.
Active (Ena-
ble/Disable)
Possi-
ble
The communications setting for FSoE communications is displayed.
Selected:
Enabled
This setting assigns the Safety I/O Unit to the Safety CPU Unit as a communications
node, and displays the I/O ports for that Unit in the I/O Map.
Not selected:
Disabled
This setting does not assign the Safety I/O Unit to the Safety CPU Unit as a communi-
cations node, and does not display the I/O ports for that Unit in the I/O Map.
Device
Not
possible
This is the name of the Safety Control Unit.
Product In-
formation
Not
possible
This is the model and version of the Unit.
FSoE Slave
Address
Possi-
ble
When the Active setting described above is set to
Enabled
, the
FSoE Slave Address
is automatically set as an internal address for use with FSoE communications.
You can change the FSoE slave address. The setting range is from 1 to 65,535.
Set a unique FSoE slave address for each FSoE slave in the FSoE communications.
If the same FSoE slave address is set more than once, an error is displayed on the
Sysmac Studio.
5 System Configuration and Setup
5 - 12
NX-series Safety Control Unit User's Manual (Z930)
Содержание NX-SIH400
Страница 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Страница 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Страница 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Страница 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Страница 378: ...7 Checking Operation and Actual Operation 7 72 NX series Safety Control Unit User s Manual Z930 ...
Страница 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Страница 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Страница 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Страница 550: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 38 NX series Safety Control Unit User s Manual Z930 ...
Страница 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 558: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 46 NX series Safety Control Unit User s Manual Z930 ...
Страница 564: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 52 NX series Safety Control Unit User s Manual Z930 ...
Страница 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Страница 625: ......