Test Pulse Evaluation
The test pulse evaluation outputs a test pulse with a specific period on the 24-VDC power line from a
safety output terminal to detect errors in wiring to the externally connected device. This evaluation is
achieved through the
Test Pulse Diagnosis
parameter.
l
Test Pulse Diagnosis
The Diagnosis setting determines whether to output a test pulse with a specific period from the
safety output terminal. The parameter determines whether test pulse evaluation is used.
The errors that can be detected are determined by the parameter settings.
Refer to
Errors Detected during Self-diagnosis
on page 4 - 28 for the errors that can be detected
for each parameter setting.
Precautions for Correct Use
When the Test Pulse Diagnosis parameter is set to
with Test Pulse
, OFF pulse signals with a
pulse width of 640 μs are output while the safety output is ON to diagnose the output circuit.
Check the input response time of the connected control device to make sure it will not malfunc-
tion due to these OFF pulses.
Dual Channel Evaluation
The use of dual-channel-equivalent outputs lets you control two safety output terminals with one safety
output data from the safety program. If an error is detected in either of the two output terminals, the
outputs to the external devices are both turned OFF.
• Single Channel
Safety program
execution
Safety output data
Safety process data
communications
Safety output terminals
Device Variable
Test Pulse Evaluation
Safety CPU Unit
Safety Output Unit
I/O port
• Dual Channels
Safety program
execution
Safety output data
Safety process data
communications
Safety output terminals
Device Variable
I/O port
Test Pulse Evaluation
Test Pulse Evaluation
Safety CPU Unit
Safety Output Unit
This evaluation is achieved through the
Single/Dual
parameter.
l
Single/Dual
Set the evaluation method to use with the safety output terminals.
Setting
Description
Single Channel
The safety output terminals are used as independent safety output terminals.
4 Safety Control Unit Operation
4 - 36
NX-series Safety Control Unit User's Manual (Z930)
Содержание NX-SIH400
Страница 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Страница 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Страница 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Страница 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Страница 378: ...7 Checking Operation and Actual Operation 7 72 NX series Safety Control Unit User s Manual Z930 ...
Страница 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Страница 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Страница 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Страница 550: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 38 NX series Safety Control Unit User s Manual Z930 ...
Страница 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 558: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 46 NX series Safety Control Unit User s Manual Z930 ...
Страница 564: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 52 NX series Safety Control Unit User s Manual Z930 ...
Страница 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Страница 625: ......