6 Types and Functions of IO-Link Master Units
6 - 8
NX-series IO-Link Master Unit User’s Manual (W567)
Restoration Setting
Make this setting to restore the
parameter settings of the IO-Link
devices from the IO-Link Master
Unit.
Specify whether to enable or dis-
able restoration for each port.
00 hex
00 to 01 hex
00 hex: Disables
backup
01 hex: Enables
backup
5003 hex
01 to 04
hex
Load Rejection Output
Settings
Set whether to turn OFF outputs
from the IO-Link Master Unit
(i.e., whether to enable load
rejection) when an error occurs
in communications with the con-
troller. Make this setting for each
port.
00 hex
00 to 01 hex
00 hex: Enables load
rejection
*5
01 hex: Disables
load rejection
*6
5004 hex
01 to 04
hex
Input Filter Settings
Filters digital input values. Make
this setting for each port.
*7
3 (1ms)
0: No filter
1: 0.25 ms
2: 0.5 ms
3: 1 ms
4: 2 ms
5: 4 ms
6: 8 ms
7: 16 ms
8: 32 ms
9: 64 ms
10: 128 ms
11: 256
5005 hex
01 to 04
hex
Digital Input Collection
Setting
*8
Enable or disable the digital input
collection for each port in IO-Link
Mode. Digital input collection
cannot be used in SIO (DI) Mode
or SIO (DO) Mode and this set-
ting is ignored.
00 hex
00 to 01 hex
00 hex: Digital Input
Collection Disable
01 hex: Digital Input
Collection Enable
501A hex
01 to 04
hex
Offset Setting of Digital
Input Collection
*8
Specify the offset of the bit data
to be collected in the input data
from the IO-Link device, when
the digital input collection is
enabled for each port in IO-Link
Mode.
When the digital input collection
is disabled in IO-Link Mode, this
setting is ignored. This setting is
also ignored in SIO (DI) Mode or
SIO (DO) Mode.
00 hex
00 to FF hex
501B hex
01 to 04
hex
*1. You can check the codes for the IO-Link Device Configuration Settings in the manuals for the IO-Link devices.
From the Support Software, enter “#” to indicate hexadecimal followed by the hexadecimal number.
*2. Setting example: Set 11 hex for revision 1.1.
*3. Set the IO-Link input data size to a value greater than the IO-Link input data size of the device.
*4. Set the IO-Link output data size to a value greater than the IO-Link output data size of the device.
*5. Digital outputs are cleared and IO-Link communications are disabled.
*6. Digital outputs are held and IO-Link communications are maintained.
*7. Digital input values in SIO (DI) Mode and digital input values for pin 2 are specified separately for each port.
*8. These settings are supported with the unit version 1.1 or later.
Setting
Description
Default value
Setting range
Index
Subindex
Содержание NX-ILM400
Страница 12: ...Manual Structure 10 NX series IO Link Master Unit User s Manual W567...
Страница 36: ...Revision History 34 NX series IO Link Master Unit User s Manual W567...
Страница 38: ...Sections in this Manual 36 NX series IO Link Master Unit User s Manual W567...
Страница 52: ...2 Specifications 2 4 NX series IO Link Master Unit User s Manual W567...
Страница 58: ...3 Part Names and Functions 3 6 NX series IO Link Master Unit User s Manual W567...
Страница 120: ...7 Troubleshooting 7 8 NX series IO Link Master Unit User s Manual W567...
Страница 126: ...8 Inspection and Maintenance 8 6 NX series IO Link Master Unit User s Manual W567...
Страница 170: ...Appendices A 44 NX series IO Link Master Unit User s Manual W567...
Страница 171: ...I 1 I NX series IO Link Master Unit User s Manual W567 Index...
Страница 174: ...I 4 NX series IO Link Master Unit User s Manual W567 Index...
Страница 175: ......