ow is the unit panel mounted?

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

Mounting Clamp

1234567890

1234567890

123456789

123456789

Gasket

Panel

Panel

Screw to hold clamp
and unit on Panel

Fig. A

Fig. B

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

P

ower Supply

The power supply to the NT2S-SF123B-EV2 is from the PLC.  The figure below
shows the connection between the PLC and the unit through a cable.

PLC PORT

DB9  MALE

CONNECTOR

Connecting

Cable

DB9  FEMALE

CONNECTOR

To PLC

Programming Port

PLC

Page 8

Page 13

Page 6

Page 15

G

eneral:

The 

NT2S-SF123B-EV2 is intended to be used as a low cost Operator

interface for PLCs which are rich in program memory or data memory
areas such as the Omron C Series PLCs.

The 

NT2S-SF123B-EV2 has the following features:

Feature

NT2S-SF123B-EV2

Display

Backlit 2X16 LCD

LEDs

2

Keys

6

ASCII screens

32 characters

Embedded variables

16

Each key is mapped from work bits 201.00 to 201.05.  Every time a key is
pressed, the corresponding bit as shown in the table below is held on while
the key is pressed.  The keys also have alternate functions.

Key

Work Bit Register mode function

F1/REG

201.00

Changes register prefix

F2/DATA

201.01

Enters data entry mode

F3/DOWN

201.02

Increments register number or data

depending on mode

F4/UP

201.03

Decrements register number or data
depending on mode

F5/CLR

201.04

Clears data field to 0 / Register field to
 first register value

F6/ENT

201.05

Accepts new data and sends to the PLC

K

ey definitions:

g.
Put 03032E03H in words DM0213 and DM0214.  The 

NT2S-SF123B-EV2

will read data in DM0003 and embed in xx.x format.

h.
Move “s “ into DM0215.  This command completes the screen by
appending the “s ” to bake time.

This will put the following data in the data words below:
("b" is used for a space, i.e. 20H)

Word

ASCII

Hex

Word

ASCII

Hex

DM0200 Do

#446F

DM0208 BA

#4241

DM0201 or

#6F72

DM0209 KE

#4B45

DM0202 :b

#3A20

DM0210 TI

#5449

DM0203 CL

#434C

DM0211 ME

#4D45

DM0204 OS

#4F53

DM0212 :b

#3A20

DM0205 ED

#4544

DM0213

#0303

DM0206 bb

#2020

DM0214

#2E03

DM0207 bb

#2020

DM0215  sb

#7320

B

ar Graph:

NT2S-SF123B-EV2 uses DM0012 to DM0015 registers to hold bar graph
values to be displayed.  If Offset register points to DM0200 then put
Hex value 0C0C into DM0200 onwards to display bar graph with the
value in DM0012.

Example:
Put 0C0C into DM0200, DM0201, DM0202, DM0203 and 200 into
DM0020.  This will display bar graph 8 characters wide.  Maximum
length is 16 characters.  Each character on display can display five
vertical lines.  To display full bar graph put # 80 into DM0012 and
0C0C from DM0200 to DM0207.
To display Bar Graph with value in DM0013, put 0D0D in DM0200
onwards.

R

egister mode:

In the register mode, the operator can access all the registers and bits
in the PLC.

By pressing the REG key, the operator can scroll through the register
prefixes.  By using the UP / DOWN keys, the register numbers can be
accessed.  Data can be changed in the registers by pressing the DATA
key.  The data field will blink to indicate that the unit is ready to accept
new data.  At this time, the UP / DOWN keys can be used to edit data
followed by the ENT key.

It is advisable to create a “password” screen which can block the usage
of the register mode.