7
.
EtherNet/IP Connection Procedure
37
7.3.5. Setting the Connections
Set the target variables (that receive the open request) and the originator variables (that
request for opening), and then set the connections (tag data link table).
1
Click the
Connection
Button on
the Built-in EtherNet/IP Port
Settings Connection Settings
Tab Page.
2
Right-click any open space in
Connection and select
Add
from
the menu.
3
A new connection can be
entered. Select the newly added
entry cell.
Select
192.168.250.50
from the
pull-down list of Target Device.
4
The default_001 connection is
created.
Check that Consume Data
From/Produce Data To is
selected in the
Connection I/O
Type
Column.
5
The target variable and the
originator variable can be set.
6
Click the entry cell for Input in
the
Target Variable
Column.
When you press
Ctrl
+
Space
on the keyboard, an appropriate
instance number appears.
*The instance number also
appears even when the first
character of the instance
number ''1'' is entered.
Select the instance number.
Likewise, set the target variable
for Output.
Содержание NJ501-1500