D-7
NE1A/DST1
Specifications
NE1A-SCPU01
General Specifications
Safety Input Specifications
Safety Output Specifications
Test Output Specifications
Note: Total simultaneous ON current: 1.4 A
Standards
Note: For details on operating precautions and other information required to
use the product, be sure to read the following operation manual:
DeviceNet Safety Network Controller Operation Manual (Z906)
DST1-
@
SL-1
General Specifications
Safety Input Specifications
Note: For details on operating precautions and other information required to
use the product, be sure to read the following operation manual:
DeviceNet Safety DST1-series Safety I/O Terminals Operation Manual
(Z904)
Safety Output Specifications
Test Output Specifications
Safety Output Specifications for Realy Outputs
Standards
DeviceNet communications
power supply voltage
11 to 25 VDC (supplied from communications
connector)
Unit power supply voltage
20.4 to 26.4 VDC (24 VDC 15% +10%)
I/O power supply voltage
Consumption
current
Communica-
tions power
supply
24 VDC, 15 mA
Internal cir-
cuit power
supply
24 VDC, 230 mA
Overvoltage category
II
Noise immunity
Conforms to IEC 61131-2
Vibration resistance
10 to 57 Hz: 0.35 mm, 57 to 150 Hz: 50 m/s2
Shock resistance
150 m/s2: 11 ms
Mounting method
35-mm DIN Track
Ambient operating tempera-
ture
10 to 55°C
Ambient operating humidity 10% to 95% (with no condensation)
Ambient storage tempera-
ture
40 to 70°C
Degree of protection
IP20
Weight
460 g max.
Input type
Sinking inputs (PNP)
ON voltage
11 VDC min. between each input terminal and G1
OFF voltage
5 VDC min. between each input terminal and G1
OFF current
1 mA max.
Input current
4.5 mA
Output type
Sourcing outputs (PNP)
Rated output current
0.5 A max. per output
Residual voltage
1.2 V max. between each output terminal and V2
Leakage current
0.1 mA max.
Output type
Sourcing outputs (PNP)
Rated output current
0.7 A max. per output (See note.)
Residual voltage
1.2 V max. between each output terminal
and V1
Leakage current
0.1 mA max.
Certifying body
Standards
TÜV Rheinland
EN954-1:1996, EN60204-1:1997, EN61000-6-2:2001,
EN61000-6-4:2001, EN418:1992, IEC61508 part1-7/
12.98-05.00, IEC61131-2/02.03, NFPA 79-2002, ANSI
RIA15.06-1999, ANSI B11.19-2003
UL
UL1998 (pending), NFPA79 (pending), UL508, CSA22.2
No14, UL1604
DeviceNet communications
power supply voltage
11 to 25 VDC (supplied from communications
connector)
Unit power supply voltage
20.4 to 26.4 VDC (24 VDC 15% +10%)
I/O power supply voltage
Consumption
current
Communica-
tions power
supply
DST1-ID12SL-1/MD16SL-1: 100 mA
DST1-MRD08SL-1: 110 mA
Overvoltage category
II
Noise immunity
Conforms to IEC 61131-2
Vibration resistance
10 to 57 Hz: 0.35 mm, 57 to 150 Hz: 50 m/s2
Shock resistance
DST1-ID12SL-1/MD16SL-1: 150 m/s² 11 ms
DST1-MRD08SL-1: 100 m/s² 11 ms
Mounting method
35-mm DIN Track
Ambient operating tempera-
ture
10 to 55°C
Ambient operating humidity
10% to 95% (with no condensation)
DST1-MRD08SL-1: 10% to 85% (with no con-
densation)
Ambient storage tempera-
ture
40 to 70°C
Degree of protection
IP20
Weight
DST1-ID12SL-1/MD16SL-1: 420 g
DST1-MRD08SL-1: 600 g
Input type
Sinking inputs (PNP)
ON voltage
11 VDC min. between each input terminal and G1
OFF voltage
5 VDC min. between each input terminal and G1
OFF current
1 mA max.
Input current
6 mA
Output type
Sourcing outputs (PNP)
Rated output current
0.5 A max. per output
Residual voltage
1.2 V max. between each output terminal and V2
Leakage current
0.1 mA max.
Output type
Sourcing outputs (PNP)
Rated output current
0.7 A max. per point
Residual voltage
1.2 V max. between each output terminal and V1
Leakage current
0.1 mA max.
Relays
G7SA-2A2B, EN 50205 Class A
Minimum applicable load
1 mA at 5 VDC
Rated load for a resistive
load
240 VAC: 2 A, 30 VDC: 2 A
Rated load for an inductive
load
2 A at 240 VAC (cos =0.3),
1 A at 24 VDC
Mechanical life expectancy
5,000,000 operations min. (switching frequency
of 7,200 operations/h)
Electrical life expectancy
100,000 operations min. (at rated load and
switching frequency of 1,800 operations/h)
Certifying body
Standards
TÜV Rheinland
EN954-1/12.96, EN60204-1/12.97, EN61000-6-2/10.01,
EN61000-6-4/10.01,EN418/1992, IEC61508 part1-7/
12.98-05.00,IEC61131-2/02.03, NFPA 79-2002,ANSI
RIA15.06-1999, ANSI B11.19-2003
UL
UL1998, NFPA79, UL508, CSA22.2 No14, UL1604
(DST1-ID12SL-1 and DST1-MD16SL-1 only)