3 Installation and Wiring
3 - 18
NA-series Programmable Terminal Hardware(-V1) User’s Manual (V125)
• To avoid overheating the conduits when using conduits for wiring, do not place wires for a single
circuit in separate conduits.
• Power cables and signal cables adversely affect each other. Do not wire them in parallel.
• Noise induction may occur if the NA Unit is installed in a panel that includes high-voltage devices.
Wire and install them as far apart as possible.
• Either install the NA Unit a minimum of 200 mm away from high-voltage lines or power lines, or
place the high-voltage lines or power lines in metal tubing and completely ground the metal tubing
to 100
Ω
or less.
Parallel Wiring (Single Phase)
Correct
Correct
Power supply
Incorrect
Power supply
Power supply
Load
Load
Load
Example: Separating NA Unit from Power Lines
Metal tubing
200 mm
200 mm
High-voltage power panel
Power lines
Power lines
Ground of
100 Ω or less
NA Unit
NA Unit
Содержание NA-series
Страница 8: ...Sections in this Manual 6 NA series Programmable Terminal Hardware V1 User s Manual V125 ...
Страница 12: ...CONTENTS 10 NA series Programmable Terminal Hardware V1 User s Manual V125 ...
Страница 82: ...3 Installation and Wiring 3 22 NA series Programmable Terminal Hardware V1 User s Manual V125 ...
Страница 164: ...5 Troubleshooting 5 18 NA series Programmable Terminal Hardware V1 User s Manual V125 ...
Страница 179: ...I 1 I NA series Programmable Terminal Hardware V1 User s Manual V125 Index ...
Страница 181: ......