2.5 Wiring
2-27
Preparation
●
CT input
PMU1A
(Electric
power)
PMU2A
(Power
two-system)
EMU8A
(Pulse/temperature)
CTD8E
(CT
expansion)
○
○
×
○
O: With input X: Without input
[PMU1A (electric power)]
When connecting dedicated CT, perform wiring as follows: between terminals [13] and [14],
[15] and [16], and [17] and [18] in single-phase 2-wire; phase R between terminals [13] and
[14] and phase T between terminals [17] and [18] in single-phase 3-wire or 3-phase 3-wire;
phase R between terminals [13] and [14], phase S between terminals [15] and [16], and
phase T between terminals [17] and [18] in 3-phase 4-wire.
In this case, terminals [13], [15], and [17] are specified as S, and terminals [14], [16], and [18],
as L.
Single
phase
2-wire
Single
phase
3-wire
3-phase
3-wire
3-phase
4-wire
CT1([13]-[14]) L
R
R
R
CT2([15]-[16]) L
-
-
S
CT3([17]-[18])
L T T T
Number of
measurement
circuits
3 circuits
1 circuit
1 circuit
1 circuit
[PMU2A (power two-system)]
When connecting dedicated CT to system 1, perform wiring as follows: between terminals
[13] and [14] and [15] and [16] in single-phase 2-wire; R phase between terminals [13] and
[14] and phase T between terminals [15] and [16] in single phase 3-wire or 3-phase 3-wire.
When connecting dedicated CT to system 2, perform the wiring as follows: between terminals
[17] and [18] in single-phase 2-wire; phase R between terminals [17] and [18] and phase T
between terminals [19] and [20] in single-phase 3-wire or 3-phase 3-wire.
In this case, terminals [13], [15], [17], and [19] are specified as S, and terminals [14], [16], [18],
and [20], as L.
Single
phase
2-wire
Single
phase
3-wire
3-phase
3-wire
CT1([13]-[14]) L
R
R
CT2([15]-[16]) L
T
T
CT3([17]-[18]) L
R
R
CT4([19]-[20]) L
T
T
Number of
measurement
circuits
4 circuits 2 circuits
2 circuits
*
In PMU2A, CT1 and CT2 are assigned for measurements in system 1, and CT3 and CT4
are assigned for measurements in system 2. If, for example, 4 circuits are measured in
single-phase 2-wire, CT1 to CT4 are used. Cross-wiring is therefore required between
systems 1 and 2.