Section 5 Functions and Operations
5-44
5.12 Outputting for a Set Interval
The shot output function turns OFF a comparative output after a set
interval after it turns ON. The following diagram shows operation when
the shot output is set to 100 ms on the K3HB-R.
The shot output time is set using the following parameter.
* The unit for K3HB-R settings is 100 ms. For example, if 10 is set,
then the shot output time is 10
×
100 ms = 1 s.
The shot output time is an internal calculation time. The following times
are added to the set time to give the actual output time.
• For relay outputs: 11 ms max.
• For transistor outputs: 1 ms max.
Advanced function setting level
Parameter
Set value
Meaning of set value
Shot output
shot
0
to
1999
0 to 1,999 ms (0 to 199.9 s)*
The shot output will be
disabled when set to 0.
R P
C
Comparative
set value H
Comparative
set value L
Output H
Output L
100 ms
100 ms
Measurement value
shot
L
f
(SHOT)
Содержание K35-2
Страница 2: ......
Страница 24: ...Outline Section 1 Outline 1 8 ...
Страница 25: ...2 1 Preparations Section 2 Preparations 2 1 Mounting 2 2 2 2 Using I O 2 4 ...
Страница 54: ...Basic Application Methods Basic Application Methods Section 3 Basic Application Methods 3 18 ...
Страница 62: ...Initial Setup Section 4 Initial Setup 4 8 ...
Страница 148: ...Functions and Operations Section 5 Functions and Operations 5 86 ...
Страница 149: ...6 1 Troubleshooting Section 6 Troubleshooting 6 1 Error Displays 6 2 6 2 Countermeasures 6 3 ...
Страница 152: ...Troubleshooting Section 6 Troubleshooting 6 4 ...
Страница 185: ......