Temperature Controller CompoWay/F Driver
GP-Pro EX Device/PLC Connection Manual
17
Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings]
.
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.
Settings of External Device
Use the level key, mode key, down key and up key in front of the Temperature Controller for communication
settings of the External Device.
Please refer to the manual of the Temperature Controller for more details.
Procedure
1. Use the rotary switch in front of the Temperature Controller to set Unit No. (UNIT) and Speed (BPS).
2. Press and hold the level key (3 minutes or more) in front of the Display to transfer from the operation level to
the default level.
3. Press the level key several times to transfer from the default level to the communication setting level.
4. Press the mode key to select the parameter.
5. Press the down/up keys to change the setting.
6. Press and hold the level key to transfer to the operation level.
Setting Value
•
Setting of the rotary switch of the Temperature Controller
•
Setting of the display exclusive for the Temperature Controller
• Set the HOST link unit No. for "Unit No.".
UNIT
1
BPS
1
LEN
7
SBIT
2
PRTY
EVEN
SDWT
20
• Parameters to be set vary depending on the Temperature Controller. Please refer to the manual of
the Temperature Controller for more details.
• Set Wait to Send to 20ms or more. Finely adjust Wait to Send according to the communication
status.