48
48
Step1
1
OFF
ON
2 3 4 5 6 7 8
Step2
MODE
MODE
dip
1off
U
1
U
1
MODE
MODE
Step3
MODE
MODE
2280.00
2280.00
2280.00
2000.00
MODE
2300.00
SET1
SET2
MODE
2280.00
2280.00
MODE
2300.00
SET
Ratings (Specifications)
Conformance to EN/IEC Standards
1
6
*1:
After reaching the last set value, the
U
Key will scroll to the first set value.
Models Other Than H7CX-R11W
@
in Tachometer Mode
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC (U.S.A.)
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD. (SINGAPORE)
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
Input Connections
No-voltage Inputs (NPN Inputs)
Voltage Inputs (PNP Inputs)
Open Collector
Voltage Output
Contact Input
Note: Operate with transistor ON
Note: Operate with transistor ON
Note: Operate with relay ON
0 V
Hold Count
PLC or
sensor
Sensor
0 V
Hold Count
0 V
Hold Count
No-contact Input
(NPN Transistor)
Contact Input
No-contact Input
(PNP Transistor)
Sensor
Sensor
0 V
Hold Count
0 V
Hold Count
0 V
Hold Count
Note: Operate with transistor OFF
Note: Operate with transistor ON
Note: Operate with relay ON
Digital Tachometer
Power supply voltage
100 to 240 VAC, 50/60 Hz (Other than H7CX-R11
@
D1)
12 to 24 VDC/24 VAC, 50/60 Hz (H7CX-R11
@
D1)
Allowable voltage fluctuation range 85% to 110% of rated supply voltage (12 to 24 VDC: 90% to 110%)
Power consumption
Approx. 9.4 VA at 100 to 240 VAC,
C
D
V
4
2
o
t
2
1
/
C
A
V
4
2
t
a
W
7
.
4
/
A
V
2
.
7
.
x
o
r
p
p
A
Operating temperature range
−
10 to 55°C (
−
10 to 50°C if Tachometer are mounted side by side)
(with no icing or condensation)
Storage temperature range
−
25 to 70°C (with no icing or condensation)
Operating humidity range
25% to 85%
Altitude
2,000 m max.
Recommended fuse
T2A, 250VAC, time-lag, low-breaking capacity
Weight
Approx. 110 g (main unit only)
Installation environment Over-voltage category II, pollution degree 2. (IEC 61010-1)
Input method
No-voltage input ON impedance: 1 k
Ω
max. (Leakage current: 12 mA when 0
Ω
)
ON residual voltage: 3 V max.
OFF impedance: 100 k
Ω
min.
Voltage input
High (logic) level: 4.5 to 30 VDC
Low (logic) level: 0 to 2 VDC (Input resistance: approx. 4.7 k
Ω
)
No-voltage (NPN) input/voltage (PNP) input (switchable)
Control output
Contact output 250 VAC, 3 A (resistive load)
30 VDC, 3 A (resistive load)
Electrical life of relay
100,000 operations (at an ambient temperature of 23°C)
Mechanical life of relay
10,000,000 operations (at an ambient temperature of 23°C)
External power supply
12 VDC, 100 mA
Degree of protection
IEC IP66, UL508 Type 4X *
* Individual mounting:
Degree of protection on the front panel of the
Tachometer conforms to
UL 508 Type 4X when all of the following conditions are satisfied:
The Y92S-29 waterproof packing and Y92F-30 mounting adapter are used with the
Tachometer. Use only these parts for replacement.
The Tachometer is mounted on the flat surface of an enclosure that is rated and marked
"Type 4X for Indoor Use Only."
Self-diagnostic Functions
The following displays will appear if an error occurs.
Main display
ffffff
*3
e1
e2
e2
e3
*
4
Sub-display
No change
OFF
OFF
No change
Description
Measurement value
overflow*2
CPU error
Memory error (RAM)
Memory error
(EEP-ROM)*1
Output Counter Overflow
Output status
No change
OFF
OFF
OFF
No change
Correction method
Measurement value
≤
999999
Either press the hold
key or reset the power supply.
Turn ON the power again
Hold key
Hold Key
Set value after reset
No change
No change
No change
Factory setting.
No change
*1. This includes times when the life of the EEPROM has expired.
*2. Occurs when the measurement value reaches 999,999.
*3. Display flashes (1-second cycles).
*4. The normal display and
e3
will appear alternately.
When the Hold Key is pressed,
e3
with no longer be displayed even if the alarm set value is exceeded.
(Monitoring is possible, however, because the counter will continue without clearing the output ON count.)
89.9
7.5
Panel
Y92F-30 (order separately)
Flush Mounting Adapter
Y92S-29 (order separately)
Waterproof Packing
(51)
Flush Mounting
Mounting Dimensions (Unit: mm)
Mounting and Panel-cutout Dimensions Diagram
58
15 min.
60 min.
Panel-cutout Dimensions Diagram
(Unit: mm)
Panel cutouts are as shown below
(according to DIN43700).
To allow easier operation, it is recommended
that Adapters be mounted so that the gap
between sides with hooks is at least 15 mm
(i.e., with the panel cutouts separated by at
least 60 mm).
Note 1: The mounting panel thickness should
be 1 to 5 mm.
A
A (48n 2.5)
1
0
n Units mounted
side-by-side
H7CX-R
@
-N
100.9
103.2*
Surface Mounting
1st digit
6th digit
Operation Keys
7. Mode Key
(Used to switch mode and setting items.)
Display Section
1. Hold Indicator (orange)
(Lit when the hold input or hold key is ON.)
2. Key Protect Indicator (orange)
Lit when the key protect switch is ON.
3. Control Output Indicator (orange)
OUT (1-output models)
OUT 1 2 (2-output models)
4. Comparison Value 1, 2 Stage
Indicator
5. Present Value (Main Display)
Character height: 10 mm (red)
6. Comparison Value (Sub-display)
Character height: 6 mm (green)
Wire properly after checking the specifications of the power supply voltage.
Terminal Arrangement
Nomenclature
Refer to the
table on the right.
NPN/PNP
input mode
1
2
3
4
5
6
7
8
Parameters must be set using both the DIP switch and the operation keys
on the front panel. Refer to the following for the detailed procedure.
Set the basic parameters.
(Factory setting)
OFF
NPN
ON
PNP
OFF
ON
OFF
ON
Pin 3
OFF
ON
OFF
ON
Pin 5
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Pin 4
OFF
OFF
ON
ON
Pin 6
OFF
OFF
ON
ON
Tachometer
AMD compatible
Tachometer
AMD compatible
Output mode
Upper and lower limit
Area
Upper limit
Lower limit
Average processing
OFF (no average processing)
2 times
4 times
8 times
30 Hz
10 ms
10 kHz *2
1 ms
The settings made using the DIP switch can be checked in the DIP switch monitor mode.
Change to Function Setting Mode.
DIP switch
monitor mode
1 s min.
1 s min.
+
+
3 s min.
3 s min.
Function
setting mode
Run mode
Power ON
Function setting mode
Display
dp
pscl
avgt
auto0
dhld
hys
offd
sl-h
k
ypt
Models other than “-R11W
@
” Models
on-a
on-c
“-R11W
@
” Models
on1a
on2a
on1c
on2c
Parameter name
Decimal point
position
Prescale value
Averaging method
Auto-zero time
Startup time
Peak/bottom
hold enabled
Output
hysteresis
Output OFF delay
Set value upper limit
Key protect
level
Output ON count
alarm set value
Output ON
count monitor value
Output 1 OUT1) ON
count alarm set value
Output 2 OUT2) ON
count alarm set value
Output 1 OUT1) ON
count monitor value
Output 2 OUT2)
ON count monitor value
Set value
Displayed only when the mode is
not AMD compatible mode.
Displayed only when the mode is
not AMD compatible mode. Unit: second
Unit: second
The position of the decimal point for the
value after prescaling will be set according
to the decimal point position setting.
Unit: Second
×
1,000
The monitor value is only displayed.
It cannot be set.
×
1,000
×
1,000
×
1,000
The monitor value is only displayed.
It cannot be set.
×
1,000
The monitor value is only displayed.
It cannot be set.
×
1,000
Set value
------
,
-----.-
,
----.--
,
---.---
*1
0.001
to
1.000
to
99.999
,
*1
0.1
to
999.9
0.0
to
99.9
off
,
on
*1
0
to
99999
0.00
to
19.99
1
to
999999
k
p-1
,
k
p-2
,
k
p-3
,
k
p-4
,
k
p-5
,
k
p-6
,
k
p-7
*1
0
to
9999
0
9999
0
to
9999
Output Mode Setting
Set the parameters that cannot be set with the DIP switch.
Set the parameters using the
U
Key.
The characters displayed in reverse video are the default settings.
Set the comparison values after switching from function setting mode to run mode.
Output Mode: Upper/
Lower Limit or Area
Output Mode:
Upper Limit or Lower Limit
Measurement value
Measurement value
Measurement value
Comparison value 1
Measurement value
Comparison value
Measurement value
Comparison value 2
Converting from the AMD-S to the H7CX-R11-N
Settings
Terminal Arrangement and Wiring Connections
3
4
5
6
2
1
8
7
Sensor
Tc Ta
100/110 VAC
(200/220 VAC)
Tb
8PFA
Black (white)
Brown
(red)
Blue
(black)
5
4
6
7
8
2
3
1
11
10
9
HOLD
HOLD
Sensor
Tb Ta
100 to 240 VAC
Tc
P2CF-11
Black
(white)
Brown (red)
Blue
(black)
Connection Sockets: 8PFA
Connection Sockets: P2CF-11
AMD-S
H7CX-R11-N
Models Other Than H7CX-R11W
@
in AMD Compatible Mode
a
b
*If time “a” is exceeded during operation, the output will turn ON. If time “b” is exceeded during
operation, the output will turn OFF. (If average processing is enabled, the output operation will be
performed when the time is exceeded once.)
ON condition for output 1: CP1 present value (display value)
≥
Comparison value 1
ON condition for output 2: CP2 present value (display value)
≥
Comparison value 2
ON condition for output 1: CP1 present value (display value)
≤
Comparison value 1
ON condition for output 2: CP2 present value (display value)
≤
Comparison value 2
Upper
limit
(HI-HI)
Lower
limit
(LO-LO)
H7CX-R11W
@
Output 1
Output 1
Output 2
Output 2
OUT1
CP1 display
value
Comparison
value 1
OUT2
CP2 display
value
Comparison
value 2
OUT1
CP1
display value
Comparison
value 1
OUT2
CP2
display value
Comparison
value 2
Package Contents
• Digital Tachometer
• Instruction manual (this document)
P3GA-11 (order separately)
Back-connecting Socket
P2CF-11(-E) (order separately)
Back-connecting Socket
*
These dimensions vary with the
type of DIN track (reference
value).
Note 2: It is possible to mount counters side
by side, but only in the direction
without the hooks.
Note 3: If the Tachometers are mounted side by
side, water resistance will be lost.
1
3
4
5
2
6
7
8
9
Internal circuit
6
7
8
9
10
11
1
2
3
4
5
Count 2
Count 1
6
7
8
9
10
11
1
2
3
4
5
Hold*
Count
OUT
0 V
Internal circuit
12 VDC
External
power supply
H7CX-R11-N/-R11D1-N
H7CX-R11W-N/-R11WD1-N
*The hold function is the same whichever terminal is connected. Terminals are not connected
internally and so do not use them for cross wiring.
Hold*
Hold*
Sensor
(
−
)
(
+
)
(
−
)
(
+
)
Sensor
(
−
)
(
−
)
(
+
)
(
+
)
Internal circuit
External
power supply
12 VDC
0 V
OUT1
OUT2
•
When conforming to EMC standards, refer to the information provided in this
Instruction Manual for cable selection and other conditions.
•
This is a class A product. In residential areas it may cause radio interference, in
which case the user may be required to take adequate measures to reduce
interference.
•
Basic insulation is provided between power supply and input terminals and
between input and output terminals.
•
Connect the input and output terminals to devices that do not have any exposed
charged parts.
•
When double insulation is required, apply double insulation as defined in IEC
60664 that is suitable for the maximum operating voltage with clearances or
solid insulation.
Refer to the
table on the right.
Refer to the
table on the right.
Item
Input mode *1
Counting speed/Minimum
input signal width
Output mode *3
Average processing
---
---
---
* The characters displayed in reverse
video are the default settings.
Counting speed/
minimum input signal width
Input mode
Pin 2
Pin 1
Note 1: Wiring must be changed from an 8-pin socket to an 11-pin socket.
2: Take into consideration the length of the wires and the terminal numbers.
3: Order the P2CF-11Connecting Socket separately.
Key-protect Switch Settings
OFF (disable)
ON (enable)
When the key-protect switch is ON,
individual key operations can be
disabled to prevent setting errors
according to the key protect levels
(KP-1 to KP-7) shown in the
following table.
* Key protect levels are set in
function setting mode.
Key protect indicator
(Factory setting)
* Changing mode to DIP switch monitor mode or function setting mode.
Level
KP-1 (default setting)
KP-2
KP-3
KP-4
KP-5
KP-6
KP-7
*
Mode change
Invalid
Invalid
Invalid
Invalid
Invalid
Invalid
Invalid
Display switch in the run mode
Valid
Valid
Valid
Valid
Invalid
Invalid
Invalid
Hold Key
Valid
Invalid
Valid
Invalid
Invalid
Valid
Invalid
Up Key
Valid
Valid
Invalid
Invalid
Invalid
Valid
Valid
©All Rights Reserved
OMRON Corporation
1148655-4C
For details, refer to the latest datasheet (Cat. No. M079).
CAUTION
Precautions for Safe Use
Precautions for Correct Use
Indicates a potentially hazardous situation which, if not
avoided, is likely to result in minor or moderate injury or in
property damage.
Keys to Warning Symbols
SAFETY PRECAUTIONS
CAUTION
9) Do not leave the Tachometer for long periods at a high temperature with output current in the ON
state. Doing so may result in the premature deterioration of internal components (e.g., electrolytic
capacitors).
10) EEPROM is used as memory when the power is interrupted. The write life of the EEPROM is
100,000 writes. The EEPROM is written when the power is turned OFF or when switching from
function setting mode to run mode.
11) Dispose of the product according to local ordinances as they apply.
1) An inrush current of approx. 10 A will flow for a short time when the power supply is turned ON. If
the capacity of the power supply is not sufficient, the Tachometer may not start. Be sure to use a
power supply with sufficient capacity.
2) Maintain voltage fluctuations in the power supply within the specified operating voltage range.
Do not allow pieces of metal, wire clippings, or fine metallic
shavings or fillings from installation to enter the product. Doing so
may occasionally result in electric shock, fire, or malfunction.
Minor injury due to explosion may occasionally occur. Do not use
the Tachometer where subject to flammable or explosive gas.
Fire may occasionally occur. Tighten the terminal screws to the
rated torque.
P2CF Socket terminals: 4.4 lb-in (0.5 N
⋅
m)
10) Separate the Tachometer from sources of noise, such as devices with input signals from power lines
carrying noise, and wiring for I/O signals.
11) Do not connect more than two crimp terminals to the same terminal.
12) Up to two wires of the same size and type can be inserted into a single terminals.
13) Use the specified wires for wiring. Applicable Wires: AWG 18 to AWG 22, solid or twisted, copper
14) Install a switch or circuit breaker that allows the operator to immediately turn OFF the power, and label it
to clearly indicate its function.
15) When the Tachometer is operated with no-voltage input (NPN input), approximately 14 V is output from
the input terminals. Use a sensor that contains a diode.
16) Use a switch, relay, or other contact so that the rated power supply voltage will be reached within 0.1
seconds. If the power supply voltage is not reached quickly enough, the Tachometer may malfunction or
outputs may be unstable.
17) Use a switch, relay, or other contact to turn the power supply OFF instantaneously. Outputs may
malfunction and memory errors may occur if the power supply voltage is decreased gradually.
18) When changing the comparison value during operation, because the H7CX uses a constant read-in
system, the output status will change if the comparison value is changed to a value on the other side of
the present value.
19) When the power is turned ON using the factory settings, the output will turn ON after 999.9 s if no pulses
are received as count input.
20) Do not use organic solvents (such as paint thinners or benzine), strong alkali, or strong acids. They will
damage the external finish.
21) Confirm that indications are working normally, including the backlight LED, and LCD. The indicator LEDs,
LCD, and resin parts may deteriorate more quickly depending on the application environment, preventing
normal indications. Periodic inspection and replacement are required.
22) The waterproof packing may deteriorate, shrink, or harden depending on the application environment.
Periodic inspection and replacement are required.
1) When mounting the Tachometer to a panel, tighten the two mounting screws alternately, a little at a
time, so as to keep them at an equal tightness. If the panel screws are tightened unequally, water may
enter the panel.
2) Store the Tachometer at the specified temperature. If the Tachometer has been stored at a temperature
of less than
−
10
°
C, allow the Tachometer to stand at room temperature for at least 3 hours before use.
3) Mounting the Tachometer side-by-side may reduce the life expectancies of internal components.
4) Use the Tachometer within the specified ranges for the ambient operating temperature and humidity.
5) Do not use in the following locations:
•
Locations subject to sudden or extreme changes in temperature.
•
Locations where high humidity may result in condensation.
•
Locations with excessive vibration or shock.
•
Locations subject to water.
•
Locations subject to oil.
6) Do not use this Tachometer in dusty environments, in locations where corrosive gasses are present, or in
locations subject to direct sunlight.
7) Install the Tachometer well away from any sources of static electricity, such as pipes transporting
molding materials, powders, or liquids.
8) Do not use the Tachometer outside of the rated ranges for vibration, shock, water exposure, and oil
exposure.
9) Internal elements may be destroyed if a voltage outside the rated voltage range is applied.
3) To allow for the startup time of peripheral devices (e.g., sensors), start Tachometer timing operation
200 ms to 290 ms after turning ON the power. The input signal will not be accepted before 200 to
290 ms has elapsed.
4) The input signal will not be accepted after 5 to 1005 ms has elapsed from when the power supply is
turned OFF.
5) Inrush current generated by turning ON or OFF the power supply may deteriorate contacts on the
power supply circuit. Turn ON or OFF to a device with the rated current of more than 10 A.
6) The capacity of the external power supply is 100 mA at 12 V. When using a 24 VAC/12 to 24 VDC
power supply, reduce the load with the power supply voltage, as shown in the following diagram
(DC power supplies only).
The life expectancy of the output relay varies considerably according to its
usage. Use the output relay within its rated load and electrical life
expectancy. If the output relay is used beyond its life expectancy, its
contacts may become fused or there may be a risk of fire. Also, be sure
that the load current does not exceed the rated load current and when
using a heater, be sure to use a thermal switch in the load circuit.
Minor electric shock, fire, or malfunction may occasionally occur.
Do not disassemble, modify, or repair the Tachometer or touch
internal components.
0
20
10.8
15
100
Load
current
(mA)
Power supply voltage (VDC)
7) If the prescale value setting is incorrect, a counting error will occur. Check that the settings are
correct before using this function.
8) Make sure that all settings are appropriate for the application. Unexpected operation resulting in
property damage or accidents may occur if the settings are not appropriate.
45
×
45
+0.6
−
0
Characteristics
*When set to AMD mode.
Model
AMD-S
H7CX-R11-N
Item
Power supply
voltage
100 to 110 VAC
200 to 220 VAC
100 to 240 VAC
Input method
Voltage input (high: 4 to
14 V, low: 0 to 1 V)
No-voltage input/voltage
input (high: 4.5 to 30 V, low:
0 to 2 V)
External power
supply
12 VDC
±
1 V, 12 mA
12 VDC (
±
10%), 100 mA
Relay output
5 A at 200 VAC (resistive
load)
3 A at 250 VAC/30 VDC
(resistive load)
Output mode
Rotation increase (AMD-
SU
@
)
Rotation decrease (AMD-
SL
@
)
HI-LO, AREA, HI-HI, LO-LO
(Set using DIP switch.)
Setting method
*
Input pulse interval (s)
Input pulse interval (s) *
Detection rota-
tion rate range
6 to 6,000 rpm
(for 1 pulse/rotation)
0.00006 to 20,000 rpm *
(for 1 pulse/rotation)
Startup time
Always from 0.1 to 10 s
(Always 10 s if not
specified.)
Setting range: 0.0 to 99.9 s
Life expectancy
Output relay electrical
operations of 500,000 min.
Output relay electrical
operations of 100,000 min.
Memory backup None
EEPROM (overwrites:
100,000 times min.)
Setting Procedure
Perform the following settings to achieve the functions of the
AMD-S using the H7CX-R11-N.
DIP Switch Settings
Operation Key Settings
Note:
The characters displayed in reverse video are the default settings.
Model
AMD-S
H7CX-R11-N
Item
DIP switch pin status
Set value
Measuring
ranges
1 ms
10 ms
Output
mode
Upper
limit
Average
processing
None
Input mode Voltage Input
Model
AMD-S
H7CX-R11-N
Item
Parameters
Setting range
Set value
Startup
time
Fixed (0.1 to 10 s)
1
OFF
ON
2 3 4 5 6 7 8
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Tachometer
AMD compatible
Tachometer
AMD compatible
30 Hz
10 ms
10 kHz
1 ms
Counting Speed /
Minimum input signal width
Input
mode
Pin 2
Pin 1
1
OFF
ON
2 3 4 5 6 7 8
Lower
limit
1
OFF
ON
2 3 4 5 6 7 8
1
OFF
ON
2 3 4 5 6 7 8
OFF
1
OFF
ON
2 3 4 5 6 7 8
PNP
(STMR)
(99.9 s)
(0.0 s)
Rotation decrease
detection
(AMD-SL
@
)
Rotation increase
detection
(AMD-SU
@
)
0.01 to 0.1 s
(AMD-S
@
1),
0.1 to 1 s
(AMD-S
@
2),
1 to 10 s
(AMD-S
@
3)
Set DIP switch pin 1 to ON for
AMD-compatible mode.
Operation
Note:
Area
(AREA)
OUT
Measurement
value
OUT
Measurement
value
Comparison
value 2
Comparison
value 1
Comparison value 1
≤
Comparison value 2
Comparison value 1 >
Comparison value 2
Comparison value 1
≤
measurement value
≤
Comparison value 2
Comparison value 2
≤
measurement value
≤
Comparison value 1
Note:
Note:
OUT
OUT
Upper
and
lower
limit
(HI-LO)
Output mode
setting
Operation
Output mode
setting
Upper
limit
(HI-HI)
Lower
limit
(LO-LO)
Comparison value 2
(Upper-limit)
Comparison
value 1
(Lower-limit)
ON condition: Measurement value
≤
Comparison
value 1 or Measurement value
≥
Comparison
value 2
When comparison value 1
≥
Comparison
value 2, the output is always ON regardless
of the comparison value.
Condi-
tion
ON
condi-
tion
Operation
Output mode
setting
Operation
Output mode
setting
Area
(AREA)
Upper
and
lower
limit
(HI-LO)
Upper
limit
(HI-HI)
Lower
limit
(LO-LO)
ON condition: Measurement value
≥
Comparison value
ON condition: Measurement value
≤
Comparison value
Comparison
value
(Upper-limit)
Measure-
ment value
Measure-
ment value
Comparison
value
(Lower-limit)
Note:
OUT
Measurement
value
OUT
Measurement
value
Comparison
value 2
Comparison
value 1
Comparison value 1
≤
Comparison value 2
Comparison value 1 >
Comparison value 2
Comparison value 1
≤
measurement value
<
Comparison value 2
Comparison value 2
≤
measurement value
<
Comparison value 1
Note:
Note:
OUT
OUT
Comparison value 2
(Upper-limit)
Comparison
value 1
(Lower-limit)
ON condition: Measurement value
<
Comparison
value 1 or Measurement value
≥
Comparison
value 2
When comparison value 1
≥
comparison
value 2, the output is always ON regardless
of the comparison value.
Condi-
tion
ON
condi-
tion
ON condition: Measurement value
≥
Comparison value
ON condition: Measurement value
<
Comparison value
Comparison
value
(Upper-limit)
Measure-
ment value
Measure-
ment value
Comparison
value
(Lower-limit)
H7CX-R
@
-N
•
Installation in a Panel
H7CX is normally installed on a flat surface in an operation panel. Use a Type 1 Enclosure for the
operation panel.
•
Use the isolated source for Inputs.
•
Environment
Surrounding Air Temperature:
−
10 to 40°C
Track Mounting/Front Connecting Socket
Flush Mounting Adapter
Waterproof Packing
11-pin
11-pin, finger-safe type
---
---
P2CF-11
P2CF-11-E
Y92F-30
Y92S-29
Precautions for Compliance with UL Standards and CSA Standards
Notice to Users of the H7CX in the USA and Canada
Please use the following installation information instead of the general information in the instruction
manuals in order to use the product under certified conditions of UL and CSA when the product is
installed in the USA or Canada. These conditions are required by NFPA 70, National Electrical Code in
the USA and the Canadian Electrical Code, Part I in Canada and may vary from information given in
the product manuals or safety precautions.
INSTRUCTION MANUAL
EN
Thank you for purchasing the OMRON Product.
To ensure the safe application of the Product, read this
manual carefully before using the Product and always keep
it close at hand when the Product is in use.
(The Adapter and Waterproof Packing are
sold separately.)
•
Accessories (Order Separately)
a
b
*1. The setting is disabled (OFF) for the H7CX-R11W
@
.
*2. The value is 5 KHz for the H7CX-R11W
@
.
*3. For the H7CX-R11W
@
.
Note: Refer to the datasheet (Cat. No. M079) for detailed parameter settings.
* When set to AMD Compatible Mode
OFF
ON
Refer to the table on the right.
Refer to the table on the right.
Item
3
4
Output 1 mode
Output 2 mode
Pin 3
OFF
ON
Output mode
Upper limit
Lower limit
Pin 4
OFF
ON
Output mode
Upper limit
Lower limit
*
(Not displayed for R11W)
Suitability for Use
OMRON shall not be responsible for conformity with any standards, codes, or regulations that
apply to the combination of the products in the customer's application or use of the product.
Take all necessary steps to determine the suitability of the product for the systems, machines,
and equipment with which it will be used. Know and observe all prohibitions of use applicable to
this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE
OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN
DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY
RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT
OR SYSTEM.
See also Product catalog for Warranty and Limitation of Liability.
Minor injury due to electric shock may occasionally occur. Do not
touch any of the terminals while power is being supplied. Be sure to
mount the terminal cover after wiring.
•
•
8. Hold Key
(Used to sustain the measurement value
and output.)
9. Up Keys to
48
Contact
output
Contact
output
Use an isolated source for power input for H7CX-
@
D1.
•
to
---
---
---
---
---
---
---
---