3
H5CR
H5CR
■
Ratings
■
Characteristics
Model
H5CR-L (Basic type)
H5CR-B (Standard type)
H5CR-S (Short body type)
Rated supply voltage
100 to 240 VAC (50/60 Hz)
24 VAC (50/60 Hz)
12 to 24 VDC (permissible ripple:
20% max.)
100 to 240 VAC (50/60 Hz)
24 VAC (50/60 Hz)
12 to 24 VDC (permissible ripple:
20% max.)
Operating voltage range
85% to 110% of rated voltage
Power consumption
Approx. 3 VA at 50 Hz, 240 VAC;
approx. 1 W at 24 VDC
Approx. 5 VA at 50 Hz, 240 VAC
Approx. 2 W at 24 VDC
Reset and control signals
Min. pulse width 1 ms/20ms selectable
Gate
---
Min. pulse width: Approx. 20 ms
Key protect
---
Response time: 1 s
One-shot time
0.1 to 20 s (select from 7 kinds) or sustained
Power reset (except A-3, b-
1, and F mode)
Min. power opening time: 0.5 s
Signal, reset, gate inputs
No-voltage input
ON impedance:
1 k
W
max. (Approx. 2 mA when 0
W
)
ON residual voltage: 2 V max.
OFF impedance:
100 k
W
min.
Key protect input
---
No-voltage input
ON impedance:
1 k
W
max. (Approx. 2 mA when 0
W
)
ON residual voltage:1 V max.
OFF impedance:
100 k
W
min.
Control outputs
Contacts:
5 A at 250 VAC, resistance load (cos
f
= 1)
Transistor output: Open collector 100mA at 30 VDC max. residual voltage 2 V max. (Approx. 1 V)
Ambient temperature
–10
C to 55
C (with no icing)
Storage temperature
–25
C to 65
C (with no icing)
Ambient humidity
35% to 85%
Case
Light gray
Repeat accuracy (including temperature
and voltage effects)
Power start:
0.01%
0.05 s max.
Control signal start:
0.005%
0.03 s max. *(rate for set value)
Insulation resistance
100 M
W
min. (at 500 VDC) (between current-carrying terminal and exposed non-current-
carrying metal parts, and between non-continuous contacts)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminal and exposed
non-current-carrying metal parts) for 100 to 240 VAC type
1,000 VAC for 24VAC/12 to 24 VDC transistor output type
Surge voltage
3 kV (between power terminals) for 100 to 240 VAC type, 1 kV for 24 VAC/12 to 24 VDC
type
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
for 100 to 240 VAC type, 1.5 kV for 24 VAC/12 to 24 VDC type
Noise immunity
2 kV (between power terminals)(
480 V for 12 to 24 VDC) and
600 V (between input
terminals), square-wave noise by noise simulator (pulse width: 100 ns/1
m
s, 1-ns rise)
Static immunity
Malfunction: 8 kV; destruction: 15 kV
Vibration
Destruction
10 to 55 Hz with 0.75-mm single amplitude each in three directions
Malfunction
10 to 55 Hz with 0.5-mm single amplitude each in three directions
Shock
Destruction
294 m/s
2
(30G) each in three directions
Malfunction
98 m/s
2
(10G) each in three directions
Life expectancy
Mechanical
10 million operations min.
Electrical
100,000 operations min. (5 A at 250 VAC in load resistance)
EMC
(EMI):
EN50081-2
Emission Enclosure:
EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
(EMS):
EN50082-2
Immunity ESD:
EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:
ENV50140:
10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Conducted Disturbance: ENV50141:
10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Weight
H5CR-L: Approx. 105 g, H5CR-B: Approx. 160 g, H5CR-S: Approx. 120 g